C-mode Command Details
4-3-27 FORCED RESET – – KR
Command Format
1
0
@
x 10
x 10
Unit No. (BCD)
Response Format
Execution Conditions
Commands
Single
Multiple
OK
No
End Codes
138
Force resets the operating status of operands. (Only one bit at a time can be
force set.)
K
R
OP1 OP2 OP3 OP4
Header
Area classification
code
Classifica-
tion
CIO
LR
WR
HR
Timer
Counter
Note "SP" represents a space (20 Hex).
@
Unit No. (BCD)
Responses
Single
Multiple
RUN
OK
No
No
An end code of 14 (format error) will be returned if the length of the command
is incorrect, or if the bit is designated as other than 00 by the TIM/CNT desig-
nation.
An end code of 15 (entry number data error) will be returned if the area classi-
fication, word address, or bit parameter setting is out of range (including hexa-
decimal data).
End code (Hex)
00
01
13
14
15
18
21
3
2
1
x 10
x 10
x 10
x 10
Word address
Area classification
Charac-
Charac-
Charac-
ter 1
ter 2
ter 3
C
I
O
L
R
(SP)
W
R
(SP)
H
R
(SP)
T
I
M
C
N
T
1
0
K
R
x 10
x 10
x 16
Header
End code
code
PLC Mode
MON
PROG
OK
OK
Normal completion
Not executable in RUN mode
FCS error
Format error
Entry number data error
Frame length error
Not executable due to CPU Unit CPU error.
*
0
1
0
x 10
x 10
Bit
FCS
Terminator
Word
address
Charac-
ter 4
(SP)
0000 to 6143
(SP)
0000 to 0199
(SP)
0000 to 0511
(SP)
0000 to 0511
(SP)
0000 to 2047
(SP)
0000 to 2047
1
*
0
x 16
FCS
Terminator
UM Area
Write-protected
Read-protected
OK
Contents
Section 4-3
Bit
00 to 15
00 to 15
00 to15
00 to 15
Always
00
Always
00
OK