End Codes
Header
Name
code
WP
PROGRAM
WRITE
MI
I/O TABLE
GENERATE
QQMR
READ I/O MEM-
ORY
QQIR
REGISTER I/O
MEMORY
XZ
ABORT
(command only)
**
INITIALIZE
(command only)
IC
Undefined com-
mand (response
only)
4-2
End Codes
End Code Summary
End
Contents
code
00
Normal completion
01
Not executable in RUN mode
02
Not executable in MONITOR mode The command that was sent cannot
03
UM write-protected
04
Address over
0B
Not executable in PROGRAM mode The command that was sent cannot
13
FCS error
14
Format error
15
Entry number data error
16
Command not supported
Single-
Multiple-
Single-
frame
frame
frame
com-
command
response
mand
Valid
Valid
Valid
Valid
Not valid
Valid
Valid
Valid
Valid
Valid
Not valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
These are the response (end) codes that are returned in the response frame.
When two or more errors occur, the end code for the first error will be
returned.
Probable cause
No problem exists.
The command that was sent cannot
be executed when the PLC is in RUN
mode.
be executed when the PLC is in
MONITOR mode.
The PLC's UM is write-protected.
The program address setting in an
read or write command is above the
highest program address.
be executed when the PLC is in
PROGRAM mode.
The FCS is wrong.
The command format is wrong, or a
command that cannot be divided has
been divided, or the frame length is
smaller than the minimum length for
the applicable command.
The data is outside of the specified
range or too long.
Hexadecimal data has not been
specified.
The operand specified in an SV
Read or SV Change command does
not exist in the program.
Multiple-
RUN
MON
frame
response
Not valid
Not
Not
valid
valid
Not valid
Not
Not
valid
valid
Not valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
---
Check the relation between the com-
mand and the PLC mode.
Turn OFF pin 1 of the CPU Unit's DIP
switch (SW1).
Check the program.
This code is not currently used.
Check the FCS calculation method. If
there was influence from noise,
transfer the command again.
Check the format and transfer the
command again.
Correct the data and transfer the
command again.
Check search data or the search
starting point.
Section 4-2
PRG
UM
UM
write
read
protect
protect
Valid
Not
Valid
valid
Valid
Not
Valid
valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Valid
Corrective measures
103