RMS-SNMP01A SNMP Card
User Manual
Figure 4-4 Param. Settings (Alarm Settings)
Table 4-3 Alarm parameter settings
Item
Overtemperature
threshold
Undertemperature
threshold
Overhumidity threshold
Underhumidity threshold

4.3.4 Control Page

In the UPS information area, choose Control > System Commands and Tests to
start or shut down the UPS, as shown in
Issue 10 (2024-01-30)
NO TE
The alarm settings are valid only when an ambient T/H sensor is configured.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Default Value
40°C
0°C
90% RH
10% RH
Figure
4-5.
4 Managing the UPS on the WebUI
Value Range
30°C to 60°C
–30°C to +10°C
70% RH to 100% RH
0% RH to 40% RH
22