Figure 9-1 Setting the SNMP card IP address on the RCCMD client and SSL
encrypted transmission mode
Step 2 On the SNMP card WebUI, choose Config. > RCCMD, and set RCCMD function to
Enable. For details, see
Step 3 For a single UPS, you do not need to set the ESN. For a parallel system, set the
ESN of the UPS in which the SNMP card is located on the page.
Step 4 On the SNMP card WebUI, the SSL encryption is set to Enable by default and does
not need to be set. If the RCCMD client is set to the unencrypted mode, you need
to set the SSL encryption to Disable on the SNMP card WebUI.
Step 5 Configure events. If you set the job type to RCCMD Message under Inverter on,
specify the IP address and port of the RCCMD client. The port is 6003 by default. If
you modify the port, you also need to modify it on the RCCMD client to keep
them consistent. Enter the message to be sent and set the message sending
mechanism. For example, set it to Immediately, once.
Step 6 On the Monitoring > Control page, start the UPS, and the inverter mode will be
triggered. Send the message indicating that the inverter is on.
Step 7 On the RCCMD client, you can view messages through the View Event Log at the
upper left corner.
----End