RMS-SNMP01A SNMP Card User Manual Issue Date 2024-01-30 HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
About This Document About This Document Purpose This document describes the RMS-SNMP01A in terms of its features, appearance, installation, usage, and operation. The RMS-SNMP01A is an optional communications card designed for the UPS2000-H-(6 kVA–20 kVA), UPS2000-G-(6 kVA–20 kVA), and UPS2000-A-(6 kVA–10 kVA) series.
Page 7
5.1 Introduction to the NetEco 1000U..........................48 5.2 Applying for Access Rights..............................48 5.3 Managing the UPS................................48 6 Managing the UPS by Using the NMS Complying with Huawei Standard..... 49 6.1 SNMP Card Versions................................49 6.2 Installing the UPS MIB Library............................49 6.3 Managing the UPS by Using the NMS..........................
SMS. ● Works with NetShutdown, a computer and server security shutdown program developed by Huawei, to automatically shut down the computers and servers where NetShutdown is installed to protect customer data and reduce loss. ● Works with RCCMD, a client shutdown software developed by Generex, to automatically and safely shut down the clients where the RCCMD is installed to protect customer data and reduce loss.
3 Installation and Basic Settings 3.3 Installing the SNMP Card The SNMP cards for Huawei UPSs can be installed in the same way. They need to be installed behind the optional card slot cover labeled INTELLISLOT on the rear panel of the UPS.
Connecting the Standalone AI/DI Module X1.8 X2.8 3.5.3 SMS Modem The SNMP card can be configured with an SMS modem provided by Huawei. Select the model based on site requirements. Figure 3-7 shows the appearance of the SMS modem. NO TE ●...
NO TICE The user interface (UI) snapshots in this document correspond to the software version UPS2000 V200R001C91B082. The UI snapshots are subject to change without notice. Contact Huawei technical support to obtain the latest snapshots if necessary. ● Monitoring page –...
Page 43
The default SNMP port number is 161 which can be modified. NO TE If the NetEco of Huawei is used to manage the UPS, the SNMP port number must be set to 161. Click Download UPS-RFC1628-MIB on the page to download the MIB file which allows a third-party NMS complying with the RFC1628 standard, such as UNMS of Generex, to manage the UPS remotely.
● SNMP Trap is used to report alarms and collected data to the NMS and deliver parameter settings. ● If you use the Huawei NMS software, the Trap port must be set to 162. 4.5.6 RCCMD Tab Page The UPS2000 SNMP card integrates the functions of Generex RCCMD Server: ●...
4.5.1 Comm. Config Tab Page. When you load the MIB library by using the NMS, load the HUAWEI-MIB- V3.34.mib file and then the HUAWEI-UPS-MIB.mib file. For details, see the NMS user manual. 6.3 Managing the UPS by Using the NMS 6.3.1 Applying for Access Rights...