RMS-SNMP01A SNMP Card
User Manual
Issue
10
Date
2024-01-30
HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei RMS-SNMP01A

  • Page 1 RMS-SNMP01A SNMP Card User Manual Issue Date 2024-01-30 HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    About This Document About This Document Purpose This document describes the RMS-SNMP01A in terms of its features, appearance, installation, usage, and operation. The RMS-SNMP01A is an optional communications card designed for the UPS2000-H-(6 kVA–20 kVA), UPS2000-G-(6 kVA–20 kVA), and UPS2000-A-(6 kVA–10 kVA) series.
  • Page 4 ● Added the features of the external dry contact card (RMS-RELAY02B). 2016-04-30 The software version has been updated in the following aspects: ● Added the CIM feature. ● Added the RCCMD feature. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 5 ● Updated the software version. RMS- ● Changed the document name to SNMP01A V100R002 SNMP Card User Manual . 2015-08-18 This issue is the first official release. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 6: Table Of Contents

    4.4.2 Performance Data................................23 4.4.3 Historical Alarms................................24 4.5 Configuration Page................................25 4.5.1 Comm. Config Tab Page..............................25 4.5.2 User Mgmt................................... 30 4.5.3 Site Config.................................... 31 4.5.4 Performance Data Page..............................33 Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 7 5.1 Introduction to the NetEco 1000U..........................48 5.2 Applying for Access Rights..............................48 5.3 Managing the UPS................................48 6 Managing the UPS by Using the NMS Complying with Huawei Standard..... 49 6.1 SNMP Card Versions................................49 6.2 Installing the UPS MIB Library............................49 6.3 Managing the UPS by Using the NMS..........................
  • Page 8: Safety Information

    UPS output voltage level or frequency. Doing so may affect the power supply to equipment. Exercise caution when setting battery parameters. Incorrect settings will affect the power supply and battery lifespan. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 9: Overview

    UPS performance data, historical alarms, and operation logs. ● Supports optional components such as the temperature and humidity module, standalone AI/DI module, and external dry contact card. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 10: Port Description

    SMS. ● Works with NetShutdown, a computer and server security shutdown program developed by Huawei, to automatically shut down the computers and servers where NetShutdown is installed to protect customer data and reduce loss. ● Works with RCCMD, a client shutdown software developed by Generex, to automatically and safely shut down the clients where the RCCMD is installed to protect customer data and reduce loss.
  • Page 11 The SNMP card can be connected to a T/H sensor or an external dry contact card through the RS485 communications bus. Figure 2-2 TEM_HUM port Table 2-2 TEM_HUM port signal definition Component Signal Port Type Location RS485+ RJ45 Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 12 The COM port on the SNMP card is an RS485 southbound port that can connect to a standalone AI/DI module. Table 2-3 COM port signal definition Component Signal Port Type Location RS485_2+ RJ45 RS485_2- RS485+ RS485- Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 13: Installation And Basic Settings

    SNMP card, preventing ESD from damaging the SNMP card. Hold the edges of the SNMP card when you move or install it. ● Wear ESD gloves when you install the SNMP card. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 14: Installing The Snmp Card

    3 Installation and Basic Settings 3.3 Installing the SNMP Card The SNMP cards for Huawei UPSs can be installed in the same way. They need to be installed behind the optional card slot cover labeled INTELLISLOT on the rear panel of the UPS.
  • Page 15: Setting An Ip Address For The Snmp Card On The Ups Control Panel

    UPS2000-G. The control panel of the UPS2000-A does not support settings of monitoring parameters for the SNMP card. Set the parameters on the WebUI. For details, see 4.5.1 Comm. Config Tab Page. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 16 Communication Card screen. Step 5 On the Communication Card screen, press keys to set the IP address, subnet mask, and gateway for the SNMP card. ----End Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 17: Installing Optional Components

    SNMP card, and connect the other end to the T/H sensor. For details, T/H Sensor User Manual . see the Figure 3-4 shows the RJ11 terminal. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 18: Standalone Ai/Di Module

    SNMP card is configured with the AI/DI module, it can support one AI/DI signal port. This port supports 12 V DC power output. For details about other ECC500 V600R001C03 User Manual . functions and usage, see the Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 19 Single Normal mode, battery mode, mains ECO mode, or battery ECO mode Parallel All UPSs work in normal mode, battery mode, mains ECO mode, or battery ECO mode. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 20 Module (RJ45) SNMP Card Standalone AI/DI Terminal Module X1.1 RS485+ RS485_T+ X2.1 X1.2 RS485– RS485_T– X2.2 X1.3 X2.3 X1.4 RS485+ RS485_R+ X2.4 X1.5 RS485– RS485_R– X2.5 X1.6 X2.6 X1.7 X2.7 Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 21: Sms Modem

    Connecting the Standalone AI/DI Module X1.8 X2.8 3.5.3 SMS Modem The SNMP card can be configured with an SMS modem provided by Huawei. Select the model based on site requirements. Figure 3-7 shows the appearance of the SMS modem. NO TE ●...
  • Page 22: External Dry Contact Card

    Figure 3-9 shows how to connect cables to the external dry contact card. NO TE The RMS-SNMP01A card supports a T/H sensor and an external dry contact card at the same time. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 23 Figure 3-10 shows the DIP switch status of the RMS-RELAY02B. DIP switch 1 is ON and others are OFF. Figure 3-10 DIP switches Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 24: Managing The Ups On The Webui

    NO TICE The user interface (UI) snapshots in this document correspond to the software version UPS2000 V200R001C91B082. The UI snapshots are subject to change without notice. Contact Huawei technical support to obtain the latest snapshots if necessary. ● Monitoring page –...
  • Page 25: Logging In To The Webui

    Step 3 Enter https:// language, and enter the correct User Name and Password. The default user name is admin, and the preset password is Changeme. Figure 4-1 Logging in to the WebUI Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 26: Monitoring Page

    4-2. Click the device name in the upper left corner of the page to change the device name. After the change, you can confirm the new name in the dialog box that is displayed or click Enter. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 27 Displays the UPS input, output, battery parameters, energy flow diagram, environment status, and working mode. UPS information area Includes tab pages of Active alarms, Real-Time Data, Param. Settings, and Control. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 28: Real-Time Data Tab Page

    4-4. Click a text box and the range of the threshold is displayed on the right of the text box. Enter a value within the range. Table 4-3 lists the default value and value range of each threshold. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 29: Control Page

    0% RH to 40% RH 4.3.4 Control Page In the UPS information area, choose Control > System Commands and Tests to start or shut down the UPS, as shown in Figure 4-5. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 30: Query Page

    (voltage, current, frequency, and load rate) when the UPS is working. You can choose Query > Performance Data to enter the Performance Data tab page, as shown in Figure 4-7. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 31: Historical Alarms

    4.4.3 Historical Alarms Select Historical Alarms from the menu at the first level. Then you can query historical alarms in a specified time period, as shown in Figure 4-9. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 32: Configuration Page

    4.5.1 Comm. Config Tab Page On the first-level menu bar, choose Config. On the Config page, Comm. Config tab page is displayed by default. You can also choose User Mgmt., Site Config, Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 33 This function is disabled by default. If this function is enabled, you can access the SNMP card in the internal network through the external network by using a router with the NAT function. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 34 8:00, 12:00, 16:00, and 20:00. If the SNMP card is powered on within one hour after 8:00, 12:00, 16:00, or 20:00, the system will check whether the alarm notification has been Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 35 Shutdown, and there is a 12–24 V DC input. If the UPS is faulty, it does not perform the startup command when DI is set to Startup. Rectify the UPS fault first. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 36 Execute Event or Event Startup There is a 12–24 V DC input. Startup There is a 12–24 V DC input. Startup There is no input. Startup There is no input. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 37: User Mgmt

    Figure 4-14 Add User Click Modify. The Modify User dialog box is displayed, as shown in Figure 4-15. You can change the password, email and SMS language, email address, mobile Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 38: Site Config

    The SNMP card supports Secure Sockets Layer (SSL) certificate import, as shown Figure 4-19. The certificate is used for SSL encryption protection for WebUI login. You need to apply to a third-party institution for the certificate. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 39 RMS-SNMP01A SNMP Card User Manual 4 Managing the UPS on the WebUI Figure 4-16 Site Config Figure 4-17 Synchronizing time using the NTP server Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 40: Performance Data Page

    On the Performance Data page, you can set Data recording period to 10s, 30s (default), 1 min, 5 min, 10 min, 15 min, 30 min, or 60 min, as shown in Figure 4-20. Figure 4-20 Performance Data page Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 41: Snmp Tab Page

    If you select ALL, the NMS can connect to the SNMP card by using either of the preceding methods. For the three options, you need to add the NMS information in the NMS address and access permission configuration. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 42 SNMP card. The read and write communities must be different. Figure 4-23 SNMPv1&SNMPv2c read and write community settings (initial configuration) Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 43 The default SNMP port number is 161 which can be modified. NO TE If the NetEco of Huawei is used to manage the UPS, the SNMP port number must be set to 161. Click Download UPS-RFC1628-MIB on the page to download the MIB file which allows a third-party NMS complying with the RFC1628 standard, such as UNMS of Generex, to manage the UPS remotely.
  • Page 44 RMS-SNMP01A SNMP Card User Manual 4 Managing the UPS on the WebUI Figure 4-25 Adding the NMS IP address Figure 4-26 Adding the SNMP Trap Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 45: Rccmd Tab Page

    ● SNMP Trap is used to report alarms and collected data to the NMS and deliver parameter settings. ● If you use the Huawei NMS software, the Trap port must be set to 162. 4.5.6 RCCMD Tab Page The UPS2000 SNMP card integrates the functions of Generex RCCMD Server: ●...
  • Page 46 SSL Encrypted Transmission is set to Enabled by default, as shown in Figure 4-30. If it is set to Disable, the RCCMD certificate controls will not be displayed on Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 47 The SNMP card supports 17 alarm events, and a maximum of 50 jobs can be added for each event, as shown in Figure 4-32. Figure 4-32 Table 4-6 illustrate the buttons on the Event Configuration page. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 48 You can delete all jobs of a specific jobs for an event event by clicking this button. Figure 4-33 shows the buttons after one event is expanded and Table 4-7 describes these buttons. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 49 When adding a job, the job types to be selected are: RCCMD Shutdown, RCCMD Message, RCCMD Execute, and RCCMD TRAP. RCCMD Shutdown is selected by default. For different job types, you need to enter different contents. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 50 RCCMD Execute: Specify the RCCMD client IP address, port, and command to be executed. For example, enter SHUTDOWN, and the RCCMD client will shut down the computer after receiving the command. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 51 Figure 4-37 RCCMD TRAP Table 4-8 RCCMD Trap signals Signal Name Description Unit in the UPS #MODEL ESN of the UPS #OUTPOWER Active power #OUTVOLT Output voltage #OUTCURR Output current Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 52 At X seconds remaining time: When the battery backup time has only X seconds left, the job will be sent to the RCCMD client once. NO TE X and Y are variables and stand for time. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 53: Maintenance Page

    4.6 Maintenance Page 4.6.1 Data Maintenance Choose Maintenance from the first-level menu. The Data Maintenance page is displayed by default. It provides the following functions, as shown in Figure 4-39: Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 54: Upgrade Page

    On the main menu bar, click Maintenance. The Upgrade page is displayed, as shown in Figure 4-40. Figure 4-40 Upgrade page For details about the upgrade, see chapter 11 SNMP Card Upgrade. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 55: Managing The Ups By Using The Imanager Neteco 1000U

    Page. 5.3 Managing the UPS For details about how to manage the UPS by using the iManager NetEco 1000U, see the product documentation related to iManager NetEco 1000U V100R002C00 Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 56: Managing The Ups By Using The Nms Complying With Huawei Standard

    4.5.1 Comm. Config Tab Page. When you load the MIB library by using the NMS, load the HUAWEI-MIB- V3.34.mib file and then the HUAWEI-UPS-MIB.mib file. For details, see the NMS user manual. 6.3 Managing the UPS by Using the NMS 6.3.1 Applying for Access Rights...
  • Page 57: Managing The Ups

    The method for managing the UPS by using the NMS is the same as the method for managing other devices by using the NMS. For details, see the NMS user manual. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 58: Managing The Ups By Using The Nms Complying With Rfc1628 Standard

    Permission Settings is used for adding information about the NMS accessing the SNMP card, including the NMS address, access right, and Trap port. For details about how to add an NMS over a web browser, see 4.5.5 SNMP Tab Page. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 59: Managing The Ups

    Take the UNMS of Generex as an example. The method for managing the UPS by using the UNMS is the same as the method for managing other devices by using the UNMS. For details, see the UNMS user manual. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 60: Protecting The Server By Using Netshutdown

    UPS status and implement computer or server shutdown protection. One UPS system can support a maximum of 16 pieces of NetShutdown software. For details about how NetShutdown manages the UPS status, see the product documentation related to NetShutdown V100R002C00.. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 61: Protecting The Server By Using The Rccmd Software

    Figure 9-1. NO TE ● If encryption is disabled, you do not need to select the encrypted transmission. ● All configurations take effect only after restart. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 62 Send the message indicating that the inverter is on. Step 7 On the RCCMD client, you can view messages through the View Event Log at the upper left corner. ----End Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 63: Ups Alive Check Function

    UPSMAN every x seconds... is selected as the method of detecting heartbeats, set the detection parameters. The default interval is 1800s and detection is performed 100 times, as shown in Figure 9-2. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 64 Software Figure 9-2 Setting the heartbeat detection on the RCCMD client You can also manually detect the heartbeat by clicking Run alive check now, as shown in Figure 9-3. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 65 RMS-SNMP01A SNMP Card 9 Protecting the Server by Using the RCCMD User Manual Software Figure 9-3 Detecting heartbeats manually Figure 9-4 Heartbeat detected successfully ----End Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 66: Troubleshooting

    Check the browser version and the SNMP card IP address that you have entered in the address bar. SNMP card problems If the fault persists after the preceding checks, replace the SNMP card. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 67: Snmp Card Upgrade

    Select the compressed package whose file name extension is .tar.gz. Step 2 Click Send. A message of File loading may take several minutes. Continue? is displayed, as shown in Figure 11-2. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 68 If the upgrade progress is 100% and the status shows Activation succeeded., the upgrade is complete, as shown in Figure 11-5. When the upgrade is complete, the SNMP card software or software restarts. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 69 WebUI again, and click Go to Step 3 to perform the upgrade again, as shown in Figure 11-7. (In this case, you can skip Step Step 2, and Step Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 70 RMS-SNMP01A SNMP Card User Manual 11 SNMP Card Upgrade Figure 11-7 Upgrade failure scenario 2 ----End Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 71: Changing The Ssh Access Password

    Common user prorunacc: The user account is used to run service programs. Login with a password is not supported. Log in as root and run su to switch to the prorunacc account. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 72: Changing An Authentication Password

    Step 2 Run the passwd enspire command to change the password of the enspire user. Step 3 Enter a new password and re-enter it as instructed and press Enter. Figure 12-1 shows the operation screen. Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 73 Step 4 Run the su command to switch to the root user and enter the root user password, as shown in Figure 12-2. Figure 12-2 Switching to the root user Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 74 Record and keep the password properly. If you forgot the password, you cannot access the SNMP card through SSH. Figure 12-3 Changing the password of the root user ----End Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 75: A Acronyms And Abbreviations

    Liquid Crystal Display message digest algorithm 5 management information base Network Address Translation Network Management System RJ11 Registered Jack 11 RJ45 Registered Jack 45 RS485 Recommended Standard 485 secure hash algorithm Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 76 User Manual A Acronyms and Abbreviations SNMP Simple Network Management Protocol Secure Shell Secure Sockets Layer state of charge state of health TCP/IP Transmission Control Protocol/Internet Protocol uninterruptible power system Issue 10 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd.

Table of Contents