9.3 UPS Alive Check Function

Whether the RCCMD SSL encrypted transmission is enabled on the WebUI of
UPS2000 SNMP card and RCCMD client is irrelevant to the heartbeat detection
function. Only when the SSL encryption is enabled on the RCCMD client, the logs
recorded by the RCCMD client are marked with (SSL...).
On the RCCMD client, the IP address of the SNMP card that detects heartbeat
needs to be added. Then the UPS alive check function is supported; the RCCMD
can check whether the UPS and RCCMD communicate properly; the RCCMD can
receive messages sent by the SNMP card.
Procedure
Step 1 On the RCCMD client, add the IP address of the SNMP card for heartbeat
detection, as shown in
Step 2 The UPS2000 SNMP card supports both ways of heartbeat detection. If the task
configured for the SNMP card event is set to RCCMD TRAP, the RCCMD client
needs to be set to by the use of CS121/UPSMAN Traps. If by polling CS121/
UPSMAN every x seconds... is selected as the method of detecting heartbeats, set
the detection parameters. The default interval is 1800s and detection is performed
100 times, as shown in
Issue 10 (2024-01-30)