User Parameters - Beko DRYPOINTRA III 20 Translation Of Original Installation And Operation Manual

Compressed air refrigeration dryer
Table of Contents

Advertisement

DRYPOINT
®
RA III
9.3.8

User parameters

NOTE
Code
Description / explanation
drC – Local / Remote management
NO = local START-STOP mode
YES = remote START-STOP via digital input
signal
Modbus = remote START-STOP via Modbus
RTU.
HdA – High Dew Point Warning
Threshold temperature
Hdd – High Dew Point Warning
Delay time of triggering
HdS – Behaviour of device due to High
Dew Point Warning during normal
running status
NO = device doesn't stops
YES = device stops
SrV – Device maintenance timer
Setting of countdown timer
SCL – Units
°C = temperature in °C and pressure in bar
°F = temperature in °F and pressure in psi
Incorrect setting of user parameters
The incorrect setting of user parameters can lead to unexpected behaviour of the
device like improper air treatment due to wrong dew point, unexpected start and
stop, unexpected signalling of one or more warnings / alarms, condensate drain
malfunction, breakdown of Modbus communication.
Default user parameters must be modified with awareness, consistently
with the specifications and the requirements of the compressed air plant.
Original installa�on and opera�on manual
Value
Accuracy
range
NO, YES,
-
Modbus
0,0 ... 25,0 °C
or
0,5 °C or 1 °F
32 ... 77 °F
01 ... 20
1 minute
minutes
NO, YES
-
0,0 ... 9,0
0,5 (x 1000)
(x 1000)
hours
hours
°C, °F
-
Default
value
NO
20 °C or
68 °F
15
NO
8,0
°C
83 | 118