How Is Controlled The Condenser Fan; How Is Controlled The Drain Solenoid Valve; How To Display The Total Hours Of Operation; How To Change The Operating Parameters - Beko DRYPOINT RS HP50 NA Series Instructions For Installation And Operation Manual

High pressure compressed air refrigeration dryer
Table of Contents

Advertisement

Technical description

11.18.4 How is controlled the condenser fan

A temperature probe BT2 is located on the discharge side of the condenser. The condenser fan is activated (ON) when
the T2 temperature is higher than FANon setting (approx. 35°C / 96°F) and led
Condenser fan stops when T2 temperature is lower than FANoff setting (approx. 30°C/86°F).

11.18.5 How is controlled the drain solenoid valve

Drain solenoid valve is activated (ON) for Ton seconds (standard 2 seconds) every Toff minutes (standard 1 minute).
Led
shows that condensate drain solenoid valve is ON.
The condensate drain test is always active using the button
NOTE : if an electronic drainer is installed, DMC35 is set to keep always powered the drain output, Led
OFF and condensate drain test does not work.

11.18.6 How to display the total hours of operation

Total hours of operation are recorded into DMC35 and are shown through the dew point indication bar (max value
109900 hours, cannot be reset).
With dryer ON press buttons
ON
Led
is lit and a certain numbers of leds of dew point indication bar are light up. The number of leds lit define
the 1st digit of hour counter (ie : no leds lit → 1st digit =0)
Press
button, led
number of leds lit define the 2nd digit of hour counter (ie : n.3 leds lit → 2nd digit = 3)
Press
button, led
number of leds lit define the 3rd digit of hour counter (ie : n.8 leds lit → 3rd digit = 8)
Total operating hours : 0 3 8 x 100 (fixed multiplying ratio) = 3800 hours
Press
button repeatedly to scroll the displaying of 3 digits again.
Set
Press
button to exit total hours display (if no button is pressed after 30 seconds the menu is exited
automatically).

11.18.7 How to change the operating parameters

The setup menu can be used to change the dryer's operating parameters
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not
responsible for malfunctioning or failure due to modification to the operating parameters.
With dryer ON press button
Access to the menu is confirmed by led
Set
Keep
pressed and use arrows
value. Press shortly
Press
to exit setup menu (if no button is pressed after 2 minutes the menu is exited automatically).
Display
Synchronous flashing
ON
led
+ led
Non-synchronous flashing
ON
led
+ led
NOTE : parameter values are displayed on the 10 led display where 1st (left) led is the lowest limit and 10th (right) is
the highest limit.
NOTE (1) : TON set at the 10th led (right) keep drain output always powered and led
electronic drainer is installed)
28
Set
and
is lit and a certain numbers of leds of dew point indication bar are light up. The
is lit and a certain numbers of leds of dew point indication bar are light up. The
Set
for at least 2 seconds to enter the setup menu.
ON
flashing.
Set
to skip to following parameter.
Description
– drain time ON : time ON
T
ON
condensate drain valve (1)
T
- drain time OFF : pause time
OFF
for condensate drain valve
.
for at least 5 seconds.
to change the value. Release the button
1 ... 6 sec
1 ... 10 min
DRYPOINT® RS 15-550 HP50 NA
is ON.
Set
Limits
Resolution
1 sec
1 min
always off (used if
is always
to confirm the
Standard
setup
2
1

Hide quick links:

Advertisement