Original installa�on and opera�on manual
Illustration
Disconnect the high pressure gauge from the refrigerant circuit.
1.
2.
Reinstall the service panels.
Slowly open the air inlet valve.
3.
Slowly open the air outlet valve.
4.
96 | 118
Adjustment work
Description / explanation
1. Start the device and wait few minutes.
2. Turn the adjustment knob clockwise to
reduce the condensing pressure or
counterclockwise to increase it.
3. Wait for the condensing pressure to
stabilize, until the set point value
10 bar(g), +0,5/-0,5 bar (145.0 psi(g)
+7.3/-7.3 psi) is reached.
Final tasks
DRYPOINT
®
RA III