DRYPOINT
®
RA III
ALARM code
Cause
HP – Safety pressure switch HPS, the
pressure of the refrigerant fluid has
reached the safety limit.
LP – Transducer BLP, the pressure of the
refrigerant fluid has reached the
minimum value allowed. There is a
refrigerant leak in the refrigerant circuit.
Hdt – Probe BT2, the temperature of the
refrigerant fluid has reached the safety
limit.
ICE – Probe BT1, the temperature of
body of heat exchanger is under 0 °C.
PF2 – Probe BT2, defective or faulty.
PF2 – The electrical wiring between the
probe and Electronic Control Unit is
interrupted.
FLP – Transducer BLP, defective or
faulty.
FLP – The electrical wiring between the
transducer and Electronic Control Unit is
interrupted.
Transducer BHP, defective or faulty.
FHP – The electrical wiring between the
transducer and Electronic Control Unit is
interrupted.
PF1 – Probe BT1, defective or faulty.
PF1 – The electrical wiring between the
probe and Electronic Control Unit is
interrupted.
Original installa�on and opera�on manual
Action
Refer to section "16.2 Specific
malfunctions" on page 112, "Safety
pressure switch HPS has triggered".
Repair the refrigerant circuit.
Refer to section "16.2 Specific
malfunctions" on page 112, "Probe BT2,
temperature of refrigerant fluid has
reached the safety limit".
Refer to section "16.2 Specific
malfunctions" on page 112, "Probe BT1,
dew point temperature too low".
Replace the probe.
Restore the electrical wiring.
Replace the transducer.
Restore the electrical wiring.
Replace the transducer.
Restore the electrical wiring.
Replace the probe.
Restore the electrical wiring.