Original installa�on and opera�on manual
Illustration
Disconnect the low pressure gauge from the refrigerant circuit.
1.
Reinstall the service panels.
2.
Slowly open the air inlet valve.
3.
Slowly open the air outlet valve.
4.
94 | 118
Adjustment work
Description / explanation
DRYPOINT
RA III 630 ... 960/750 WC ... 960 WC
®
1. Start the device and wait few minutes.
2. Turn the adjustment screw clockwise to increase the
evaporation pressure or counterclockwise to reduce it.
3. Wait for the evaporation pressure to stabilize, until the set
point value 2,3 bar(g), +0,1/-0 bar (33.4 psi(g) +1.5/-0 psi) is
reached.
Final tasks
DRYPOINT
®
RA III