Original installa�on and opera�on manual
8.2.1

1ph+N models

NOTE
INFORMATION
1.
Establish the mains supply.
2.
Power the product acting on the ON-OFF switch. Refer to section
"3.1 Product overview" on page 18.
3.
Start the product pushing for 3 seconds the START-STOP button on the User Interface.
Refer to section "3.2 User Interface" on page 29.
4.
Check the power consumption complies with the values engraved on the type plate.
5.
Wait for the cooling fan to run.
6.
Wait until the dew point value displayed on the User Interface is stable. Refer to section
"3.2 User Interface" on page 29.
7.
Establish the compressed air supply.
8.
Slowly open the air inlet valve.
9.
Slowly open the air outlet valve.
10.
Check the air connections for air leakage.
11.
Wait for the condensate drain to works.
12.
Check the condensate drain works correctly.
68 | 118
Refrigerant compressor failure
Start and stop the device too often could damage the refrigerant compressor in an
unrepairable way.
Wait at least 5 minutes between a stop and a new start.
Start / stop actions on the device must be limited to 6 times an hour.
Dew point value
A dew point between 0 °C (+32 °F) and +10 °C (+50 °F) displayed on the User
Interface is considered to be correct according to the possible operating
conditions e.g. flow rate, air inlet temperature, ambient temperature, etc.
Commissioning work