Vertiv™ NetSure™ 731 C62 Series Power System User Manual

4.7.4 DC Settings

At the Settings screen (see Figure 4.7), press ▲ or ▼ to select the 'DC Settings' menu, and press the ENT key to enter
the screen shown in Figure 4.35.
Figure 4.35 DC Settings screen
Press ▲ or ▼ to select the parameter you need and press ◄ or ► to select the parameter value. Then press the ENT
key to confirm.
The value description of the DC parameters is listed in Table 4.14.
Table 4.14 Description of the DC parameter setting
Parameter
Range
OverVolt2
OverVolt1
40V ~ 60V
LowVolt1
LowVolt2

4.7.5 DC Rectifier Settings

At the Settings screen (see Figure 4.7), press ▲ or ▼ to select the 'DC Settings' menu, and press the ENT key to enter
the Rectifiers screen shown in Figure 4.36.
Figure 4.36 Rectifiers screen
Press ▲ or ▼ to select the parameter you need and press ◄ or ► to select the parameter value. Then press the ENT
key to confirm.
The value description of the rectifier parameters is listed in Table 4.15.
Table 4.15 Description of the rectifier parameter setting
Parameter
Range
Position En
Y, N
22
OverVolt2: 58.5V
OverVolt1: 58.5V
58.0V
LowVolt1: 45.0V
48.0V
LowVolt2: 45.0V
48.0V
Factory setting
Value description
The DC OverVolt2 alarm will be generated when the system DC voltage is higher
58.5V
than the setting value
The DC OverVolt1 alarm will be generated when the system DC voltage is higher
58.5V
than the setting value
The DC LowVolt1 alarm will be generated when the system DC voltage is lower
48.0V
than the setting value
The DC LowVolt2 alarm will be generated when the system DC voltage is lower
48.0V
than the setting value
Position En: N
HVSD:
59.0V
58.0V
Default V: 53.5V
Walk-in On:
N
Factory setting
Value description
Y: The controller will prompt you to set the rectifier position after the rectifier and
controller are powered on.
N
N: You do not need to set the rectifier position
Load Shunt:
Shunt Coeff:
No
Shunt Coeff:
- Curr:
500A
- Curr:
200A
- Volt:
25mV
- Volt:
25mv
Walk-in:
8s
Interval T:
0s
AC OverV On: N
ACCurrLim: 30A