Vertiv™ NetSure™ 731 C62 Series Power System User Manual
Item
Parameter
Default V
MpptDelta
AC Power Mode
DG Cap
DG settings
DG In
DG Relay
Start DG
Volt
BattCap En
DG control settings
BattCap
Volt En
Stop DG
Volt
BattCur En
Curr
Time En
Time
DG control settings
BattCap En
BattCap
Delay
DG Run Time
4
Range
Factory setting
48V ~ 58V
54V
0.2V ~ 3.0V
0.8V
Grid, DG,
Grid
Grid+DG
5.0KVA ~
12.5KVA
100.0KVA
None, DI1 ~ DI8
None
None, 1 ~ 8
None
13.2V ~ 60.0V
47.3V
Y, N
N
10% ~ 95%
50%
Y, N
N
40.0V ~ 54.0V
53.5V
Y, N
N
0.010C ~
0.010C
0.060C
Y, N
N
10min ~
300min
1440min
Y, N
N
50% ~ 100%
95%
0min ~ 255min
10min
Value description
Default output voltage when communication
is interrupted. Must be lower than the 'HVSD'
voltage
Output voltage delta between solar converter
and rectifier
System power supply mode, 'Grid' by default
Set it according to actual DG capacity
Dry contact input of DG running state, users
can set the DG state by referring to DI settings
in 3.7.1 Alarm Settings. For example, if you
set 'DG' In to 'DI2' and the 'Active' to 'Close',
then the DI2 input close represents the DG
start running, while the DI2 input open means
the DG is not started
Output dry contact signal of DG start/stop,
'None' by default, the hardware state is
settable
Start DG when the battery voltage is lower
than the setting value
Y: The system will determine whether start DG
according to battery remainning capacity; N:
The system will not judge the battery capacity
When the 'BattCap En' is set to 'Y', and the
current battery remainning capacity is lower
than the 'BattCap', the DG will be started
When set to 'Y', the system will judge whether
start DG according to battery voltage
When the battery voltage rises to 'Volt' and
meets the delay condition, stop the DG
When set to 'Y', the system will judge whether
stop DG according to battery charge current
When 'BattCur En' is set to 'Y', and the battery
charge current decreases to 'Curr' and meet
the delay condition, stop the DG
When set to 'Y', the system will judge whether
stop DG according to the setting time
When 'Time En' is set to 'Y', and the 'Time' is
reached, stop the DG
Y: The system will determine whether stop DG
according to battery remainning capacity; N:
The system will not judge the battery capacity
When the 'BattCap En' is set to 'Y', and the
current battery remainning capacity is lower
than the 'BattCap', stop the DG
When the battery charge current decrease to
the stop DG condition, or the battery voltage
rises to stop DG condition, and meet the delay
time continuously, the DG will be actually
stopped