Vertiv NetSure 731 C62 Series User Manual page 85

Table of Contents

Advertisement

Item
Parameter
Max
Min
Lang
Tzone
Date
Time
System Type
System
ComDownLoad
Reset PWD
Reset Para
Op1 PWD
Op2 PWD
Adm PWD
Address
Communication
BaudRate
IP/Subnet/Gate
DCEM
DCEM1
-Sh1 Curr
-Sh1 Volt
-Sh2 Curr
DCEM
-Sh2Volt
-Sh3 Curr
-Sh3 Volt
Vertiv™ NetSure™ 731 C62 Series Power System User Manual
Range
Factory setting
30min ~
1440min
2880min
5min ~ 720min
10min
Chinese,
English
English
/
/
2000 ~ 2099
/
00:00 ~ 23:59
/
48V/100
48V/300
48V/500
48V/SET
48V/1000
48V/SET
Y, N
N
Y, N
N
Y, N
N
/
/
/
/
/
/
1 ~ 254
1
1200bps ~
9600bps
9600bps
/
/
10A ~ 1000A
1000A
10mV ~ 100mV
25mV
10A ~ 1000A
1000A
10mV ~ 100mV
25mV
10A ~ 1000A
1000A
10mV ~ 100mV
25mV
Value description
After the DG is started, and continuously
running to the max. run time, the DG will be
stopped
After the DG is started, when meets the stop
condition, but the continuous run time not
reaches the min. run time, then the DG will
keep start state and until reaching the min.
run time, will the DG be stopped
Set it according to your need
Set it according to the actual instance
Set the time according to the current actual
time, regardless of whether it is a leap year or
not
Set it according to the actual instance
The system type of the controller has been set
according to the actual instance before the
controller is delivered with power supply
system. You do not need to change the value
except that the controller needs to be
replaced with a new one.
After changing the type, the controller will
restart and the other parameters will resume
the default. You need to reset and change
some parameters according to the battery and
equipment configured with the system
Whether using the Bootload serial port to
upgrade program
Whether resetting the password to the default
Whether resetting the parameter to the
default
The password can be six digits long at most. If
shorter than six digits, end it with space key
The addresses of power systems that are at
the same monitored office should be different
Make sure that the baud rates of both the
sending and receiving parties are the same
Set it according to the actual instance
Current of DCEM1 shunt1
Voltage of DCEM1 shunt1
Current of DCEM1 shunt2
Voltage of DCEM1 shunt2
Current of DCEM1 shunt3
Voltage of DCEM1 shunt3
5