Dc Settings; Rectifier Settings - Vertiv NetSure 531 AC1 User Manual

Power supply system
Table of Contents

Advertisement

32
Chapter 4 Use Of The Controller

4.7.4 DC Settings

At the Settings page, press ▲ or ▼ to select DC Settings menu. Then press ENT to enter the DC Settings page, as
shown in Figure 4-32.
Press ▲ or ▼ to select the parameter, and ◄ or ► to select the parameter value. Then press ENT to confirm.
The value description of the parameters is listed in Table 4-13.
Parameter
Over Volt
Low Volt 1
40V ~ 60V
Low Volt 2
L-Shunt En
Y, N
Shunt Coeff
1A ~ 5000A
Current
Shunt Coeff
1mV ~ 500mV
Volt

4.7.5 Rectifier Settings

At the Settings page, press ▲ or ▼ to select Rect Settings menu. Then press ENT to confirm.
There are three pages, as shown in Figure 4-33.
Press ▲ or ▼ to select the parameter, and ◄ or ► to select the parameter value. Then press ENT to confirm.
The value description of the parameters is listed in Table 4-14.
Parameter
Position En
R-Posi
HVSD
Default V
Over Volt 2: 58.5V
Low Volt 1: 58.0V
Low Volt 1: 45.0V
Low Volt 2: 45.0V
Figure 4-32 DC Settings page
Table 4-13 DC setting parameter description
Range
Factory setting
58.5V
45.0V
45.0V
N
-
-
Position En: Y
R-Posi: 1-1
HVSD:
59.0V
Default V: 53.5V
Figure 4-33 Rect Settings page
Table 4-14 Rectifier parameter description
Range
Factory setting
Y, N
Y
1 ~ 30
-
56V ~ 59V
59V
48V ~ 58V
53.5V
NetSure 531 AC1 Power Supply System User Manual
L-Shunt En: N
Shunt Coeff:
-Current: 500A
-Volt:
75mV
The DC Over Voltage alarm will be raised when the system DC output
voltage is higher than the value of Over Volt
The DC low voltage alarm will be raised when the system DC output
voltage is lower than the value of Low Volt 1. The value of the Low Volt 1
must be lower than that of the Over Volt
The DC under voltage alarm will be raised when the system DC output
voltage is lower than the value of Low Volt 2. The value of the Low Volt 2
must be lower than that of the Low Volt 1
Setting according to the actual instance
They can be reset when the shunt options are 'SET' in the system with load
shunt
Walk-in On:
N
Walk-in:
8s
Interval T:
0s
AC OverV On: N
'Y': The controller will prompt you to set rectifier position before the rectifier
and controller are powered on.
'N': You need not to set rectifier position
R-Posi: represented in two figures, the first figure represents the rectifier
number, the next figure reprents position number. Press ENT to select the
rectifier, press ◄ or ► to change position number. When the controller
communicates with the rectifier, the green indicator on the corresponding
rectifier will blink
The rectifier over voltage alarm will be raised when the rectifier output
voltage is higher than the HVSD voltage
Default output voltage when communication interrupted. Must be lower than
this value
Value description
ACCurrLim: 30A
Value description