Vertiv™ NetSure™ 731 C62 Series Power System User Manual
Item
Parameter
Const Boost -Current
Const Boost -Time
Cyc Boost -Enable
Cyc Boost -Period
Cyc Boost -Time
Charge
BoostLimitTime
management
Battery
DG Chg Limit -Enable
DG Chg Limit -Current
End Test -Volt
Battery test
End Test -Time
End Test -Cap
Cyc Test En
Cyc Test Time 1
Cyc Test Time 2
Cyc Test Time 3
Cyc Test Time 4
Short Test -Enable
Battery test
Short Test -Alarm
Short Test -Period
Short Test -Time
Battery
Stable Test -Enable
Stable Test -Current
Center Temp
Coeff
Temperature
coefficient
Temp1
Temp2
Temp3
Batt T H2
Batt T H1
2
Range
Factory setting
0.002C
~
10
0.020C
10
0.020C
10
30min ~
180min
1440min
Y, N
Y
48h ~ 8760h
2400h
30min ~
720min
2880min
60min ~
1080min
2880min
Y, N
N
0.050C
~
10
0.050C
10
0.080C
10
43.1V ~ 57.9V
45.2V
5min ~
300min
1440min
0.01C
~
10
0.70C
10
0.95C
10
Y, N
N
01-01-00:00
04-01-00:00
Month, day,
time
07-01-00:00
10-01-00:00
Y, N
N
1A ~ 100A
10A
24h ~ 8760h
720h
1min ~ 60min
5min
Y, N
N
0 ~ 9999A
9999A
10°C ~ 40°C
25°C
0 ~ 500mV/°C
72mV/°C
Batt Temp
Amb Temp,
None, Batt
None
Temp
None
-40°C ~ +100°C
50°C
-40°C ~ +100°C
50°C
Value description
The system in BC state will enter the FC state
when the charge current decreases to the
'Const Boost Current' value and after the
'Const Boost Time' value. The battery charge
voltage then will be the Float state
Enable or disable this function
The 'Cyc Boost Period' means the interval
between the two cyclic boost charge. The
battery
charging voltage is the preset 'Boost', and the
time is the preset 'Cyc Boost Time'
To ensure the system safety, the controller
will forcefully control the system to enter the
FC state from the BC state, if the boost charge
time reaches the 'BoostLimitTime'
Whether using this function
/
The controller will stop the test if the battery
voltage reaches the 'End Test Volt', or the
discharge time reaches the 'End Test Time', or
the battery capacity reaches the 'End Test
Cap'
Whether using the cyclic test function
When the parameter 'Cyc Test En' is set to 'Y',
the controller will test the battery
automatically according to the 'Cyc Test Time'
Whether using short test function
If the battery is not discharged within the
'Short Test Period', the controller will start a
short test, whose operation time is set by the
parameter 'Short Test Time'. By the end of the
test, if the difference in the discharge currents
of batteries is bigger than the 'Short Test
Alarm', the battery charge abnormal alarm
will be generated
Whether using the stable test function
Battery dischaging current upon stable test
FC voltage derated value = (Batt Temp –
'Center Temp') * Temp Coeff.
Upon alarms such as rectifier communication
interruption, DC over/undervoltage or battery
fuse alarm, the controller will not do
temperature compensation to the battery FC
voltage
Measure ambient temperature, battery
temperature, or nothing
When the detected battery temperature is
higher than Batt T H2/Batt T H1, the controller
will generate an alarm