Vertiv NetSure 731 C62 Series User Manual page 87

Table of Contents

Advertisement

Item
Parameter
User4 settings
User Name
LVD Time
User settings
LVD Shunt
Shunt Coeff-Curr
Shunt Coeff-Volt
Save Enable
Cyc Period*
Energy saving
Rect Work
Rect Limit
System Type
Fast settings
Capacity
Note*: Cyc Period, Rect Work and Rect Limit are available only when 'Save Enable' is set to 'Y'
Vertiv™ NetSure™ 731 C62 Series Power System User Manual
Range
Factory setting
CTCC, CUCC,
Other
CMCC, Other
3min ~
300min
2880min
Y, N
Y
1A ~ 2000A
100A
1mV ~ 500 mV
75mV
Y, N
N
1h ~ 8760h
48h
30% ~ 90%
90%
1 ~ 30
1
48V/100
48V/300
48V/500
48V/SET
48V/1000
48V/SET
20Ah ~ 5000Ah
600Ah
Value description
Name of User4, 'Other' by default
LVD time of User4
Whether User4 has shunt
Shunt current coefficient of User4, used with
voltage coefficient
Shunt voltage coefficient of User4, used with
current coefficient
It can be set to 'Y' when the battery is
configured and load current without instant
shock
Time of rectifier in power-on state and power-
off state, it can be set according to the actual
requirement
Output capacity percentage. More rectifiers
will start to work when larger than this setting
percentage
Minimum number of the rectifier in energy
saving state
The system type of the controller has been set
according to the actual instance before the
controller is delivered with power supply
system. You do not need to change the value
except that the controller needs to be
replaced with a new one.
After changing the type, the controller will
restart and the other parameters will resume
the default. You need to reset and change
some parameters according to the battery and
equipment configured with the system
The capacity of the batteries connected with
each shunt. You should set this parameter
according to the actual battery configuration
7