Vertiv™ NetSure™ 731 C62 Series Power System User Manual
Figure 10.2 Menu structure of the battery parameters
Bat. Settings
Basic Setting
LVD Settings
Charge
Battery Test
Temp. Comp
PowerSplit
2
Main System Information
Sys Mode: Auto
Bat. Fuse: 2
Capacity: 500AH
Bat. Shunt1: Y
Bat. Shunt2: Y
Shunt Coeff - Curr: 500A
Shunt Coeff - Volt: 25mV
Symmetry: No
Symm Alarm: 0.5V
LVD1 Enable: Y
LVD2 Enable: Y
LVD1 Volt: 44.0V
LVD2 Bolt: 43.2V
Float: 53.5V
Boost: 56.4V
Limit: 0.100C
Over: 0.300C
Auto Boost - Enable: Yes
Auto Boost - Curr: 0.060C
Auto Boost - Cap: 80.0%
Const Boost - Curr: 0.020C
Const Boost - Time: 180min
Cyc Boost - Enable: Yes
Cyc Boost - Period: 2400h
Cyc Boost -Time: 720min
BoostLimitTime: 1080min
DG Chg Limit - Enable: No
DG Chg Limit - Curr: 0.050C
End Test - Volt: 45.2V
End Test - Time: 300min
End Test - Cap: 0.700C
Cyc Test En: N
Cyc Test Time 1: 01-01-00:00
Cyc Test Time 2: 04-01-00:00
Cyc Test Time 3: 07-01-00:00
Cyc Test Time 4: 10-01-00:00
Short Test - Enable: No
Short Test - Volt: 48.0V
Short Test - Period: 720h
Short Test - Time: 5min
Stable Test - Enable: No
Stable Test - Curr: 9999A
Center Temp: 25ºC
Coeff: 72mV/ºC
Temp1: BattTemp
Temp2: No
Temp3: No
Batt T H2: 50ºC
Batt T H1: 50ºC
Batt T L1: 0ºC
PowerSplit: No
Volt: 0.5V
Curr: 60%
Coeff: 30.0
Time: 60S
DC Volt
DC Current
System Mode Alarm
Control Mode Auto
Energy Management Mode
Battery Status Float
Batt 1 Current
Remain Power
Batt 2 Current
Remain Power
AC Volts
BattTemp
FanSpeed1
FanSpeed2
Note:
1. System information is queried in system
information screen.
2. Press ESC at system information
screen, you can query the serial number
and software version of the controller.
3. Basic parameters should be reset
according to actual configuration.
4. Parameters on the right side are default
values set before delivery.