Vertiv™ NetSure™ 731 C62 Series Power System User Manual
Table 4.11 Description of the battery test parameter setting
Parameter
Range
End Test -Volt
43.1V ~ 57.9V
End Test -Time
5min ~ 1440min
End Test -Cap
0.01C
Cyc Test En
Y, N
Cyc Test Time
Month, day, time
Short Test -Enable
Y, N
Short Test -Alarm
1A ~ 100A
Short Test -Period
24h ~ 8760h
Short Test -Time
1min ~ 60min
Stable Test -Enable
Y, N
Stable Test -Current
0 ~ 9999A
The schematic diagram of the test function is shown in Figure 4.32.
Figure 4.32 Schematic diagram of the test function
Manually/
Scheduled start
battery test
Temperature compensation parameters
1. At the Batt Settings screen, press ▲ or ▼ to select the 'Temp. Comp' menu, and press the ENT key to enter the
screen shown in Figure 4.33.
Figure 4.33 Temperature compensation settings screen
20
Factory setting
45.2V
300min
~ 0.95C
0.70C
10
10
10
N
01-01-00:00
04-01-00:00
07-01-00:00
10-01-00:00
N
10A
720h
5min
N
9999A
Rectifier output
voltage lower than
Battery discharges
battery voltage
Rectifier hot
standby
Center Temp:25ºC
27°C
Coeff:
72mV/ºC
Temp1: BattTemp
Temp2: No
Amb Temp
Value description
The controller will stop the battery test and switch to FC state if the battery
voltage reaches the 'End Test Volt', or the discharge time reaches the 'End
Test Time', or the battery capacity reaches the 'End Test Cap'
Select Y to enable this function;
Select N to disable this function
When the parameter 'Cyc Test En' is set to 'Y', the controller will test the
battery according to the 'Cyc Test Time'
Whether using the short test function
The short test is used for discharge test comparation of two groups of
batteries. The inspection for the battery feature is valuable when one
battery is not discharged for a long time.
If the battery is not discharged within the 'ShortTest Period', the controller
will start a short test, whose operation time is set by the parameter
'ShortTest Time'. By the end of the test, if the difference in the discharge
currents of batteries is bigger than the 'Short Test Alarm', the battery
discharge abnormal alarm will be generated
The stable test is conducted with constant battery discharge current. To
execute the stable test, the present load current should be bigger than the
current value set by stable test. The stable test is suitable for bigger load
and relative stable load current, otherwise, do not exercise it. The current
value is set through the parameter 'Stable Test Current'. If the parameter
'StableTest Enable' is set to 'Y', the test will be started once the battery
satisfies the test condition
'End Test Volt' is reached
'End Test Cap' is reached
'End Test Time' is reached
Temp3: No
Amb Temp
Batt T H2:
60°C
50ºC
Batt T H1:
40°C
50ºC
Batt T L1:
0ºC
5°C
Battery
Auto-management