The value description of the charge parameters is listed in Table 4.10.
Table 4.10 Description of the charge parameter setting
Parameter
Range
Float
42V ~ 58V
Boost
0.100C
10
Limit
0.250C
10
0.300C
10
Over
1.000C
10
Auto Boost -Enable
Y, N
Auto Boost -
0.050C
10
Current
0.080C
10
Auto Boost -Cap
10% ~ 99%
Const Boost -
0.002C
10
Current
0.020C
10
30min ~
Const Boost -Time
1440min
Cyc Boost -Enable
Y, N
Cyc Boost -Period
48h ~ 8760h
30min ~
Cyc Boost -Time
2880min
60min ~
BoostLimitTime
2880min
DG Chg Limit -
Y, N
Enable
DG Chg Limit -
0.050C
10
Current
0.080C
10
The BC/FC switchover diagram is shown in Figure 4.30.
18
Factory setting
53.5V
56.4V
~
0.100C
10
~
0.300C
10
Y
~
0.060C
10
80.0%
~
0.020C
10
180min
Y
2400h
720min
1080min
N
~
0.100C
10
Value description
The rectifier output voltage in FC state
The rectifier output voltage in BC state
The maximum battery charging current. C
which is generally set to 10% ~ 20% of the capacity of one battery string
When the battery charging current is higher than the 'Over' value, the
controller will generate the battery charge over-current alarm
Select Y to enable this function;
Select N to disable this function
The controller will control the system to enter the BC state when the battery
capacity decreases to the value of 'To Boost Cap', or when the charging current
reaches the 'To Boost Current'. The battery charging voltage is the 'Boost' value
The system in BC state will enter the FC state automatically when the charging
current decreases to the 'Const Boost Current' value and after the 'Const Boost
Time'. The battery charge voltage then will be the Float state
Select Y to enable this function;
Select N to disable this function
The 'Cyc Boost Period' is the interval between the two cyclic BCs. The battery
charging voltage is the 'Boost' value, and the charging time is the 'Cyc Boost
Time'
During the BC state, to ensure the system safety, the controller will forcefully
control the system to enter the FC state, if the BC time reaches the
'BoostLimitTime'
Select Y to enable this function;
Select N to disable this function
The battery charge limit upon DG running
is the battery nominal capacity,
10