RMG TME 400-VM Operating Manual page 39

Hide thumbs Also See for TME 400-VM:
Table of Contents

Advertisement

Example calculation for the pressure loss of a turbine meter:
TME 400 in DN 150:
Q
= 650 m³/h
m
= 1.3 kg/m³ (natural gas at 600 mbar overpressure)
ρ
Z
(TME 400) = 5040 (see the table above)
p
Calculation:
1.4.2.11
Putting the device into operation
Note
You receive the TME 400 parameterized and calibrated according to your
specifications, so that no additionally settings are generally required.
However, check whether these settings match your specifications; check the settings
of the pulse width, the frequency reducer and the settings of the current output (for
versions with current output).
Bring all totalizers to the meter status which you desire. (see chapter 4.2 Program-
ming).
Note
Parameters can be changed exclusively with the device open.
1.4.2.12
Maintenance / lubrication
The TME 400 turbine gas meter is maintenance-free (apart from the lubrication for
meters with an oil pump).
Meters in custody transfer operation must be calibrated at the prescribed intervals
(according to national law). For meters in secondary operation, we recommend from
a metrological point of view a check at the manufacturer every 5 to 8 years.
650
2
mbar
∆p
=
5040
1
3 ,
150
4
= 5.5 mbar
Manual TME400-VMF · EN11 · January 22nd, 2024
1 Introduction
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tme 400-vmfTme 400-vcTme 400-vcf

Table of Contents