Pause

The Pause command is used to temporarily stop the execution of the program. Time of the interval can be set
using the Select time t selector in range from 0.1 second to 24 hours in increments of 0.1 second.
Please note: The Pause command:
does not stop the countdown to execute the Stop and Reset commands;
does not stop the countdown to the switch on/switch off of the relay that is set with the Output
command;
does not block the implementation of the functions performer by the special inputs A and B.
Example
Sequence 2s ON, 3s OFF is activated ten seconds after the power supply is turned on. The sequence is repeated
until the power supply is turned off.
PCS533 programmable time relay – User manual v. 1.0.1
Command: Pause
Time: 10 s
Command: Output
Mode: On
Time: 0 s
Command: Pause
Time: 2 s
Execution of the program is paused
for 10 seconds after the power
supply is turned on.
After the ten seconds pause the
Output command will be executed
that sets the relay in ON state. Time
is set to 0 which means the relay
will stay on until the next Output
command will appear.
Pause stops the execution of the
program and the activated relay for
duration of 2 seconds.