7.1.5 (Optional) Setting Parameters for the BCB Box

Prerequisites
A BCB box is installed.
Procedure
Step 1 Choose System Info > Settings > Dry Contact Set, set MUE05A connection to
Enable, and set BCB connection [OL] and Battery breaker [STA] to Enable.
Figure 7-3 BCB connection settings
----End
7.1.6 (Optional) Setting Parameters for the Top Air-Flow
Cabinet
Prerequisites
A top air-flow cabinet is installed..
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set Top outlet
cabinet to Enable.
----End

7.1.7 (Optional) Configuring the Bottom Cabling Cabinet

Prerequisites
The bottom cabling cabinet has been deployed.