Fire due to incorrect gas connection
Danger to life due to fire from an incorrect gas connection.
Follow local regulations of the gas supply company.
n
Check the type of gas available and the dynamic connection pressure
n
against the values specified on the unit.
Risk of poisoning due to faulty gas connection
Risk of poisoning from CO and other toxic gas components
Do not connect the units to networks containing carbon monoxide (CO)
n
gases or other toxic components.
Permissible CO/CO
Risk of poisoning due to excessive CO/CO
burner settings.
Always perform a flue gas analysis when commissioning gas units.
n
Document the flue gas values.
n
It is recommended that the installation site be equipped with a CO gas
n
detector.
Increased CO values due to wrong gas type
Risk of poisoning due to connection of wrong gas type
Only connect the unit to the gas type stated on the unit type plate.
n
Check the type of gas available and the dynamic connection pressure
n
against the values specified on the unit.
It is recommended that the installation site be equipped with a CO gas
n
detector.
82 / 108