Changes on components with sealing paint
Risk of injury and damage when changing components sealed with paint.
Do not change components with sealing paint (exception: CO
n
In the event of damage to the sealing paint, the affected components must
n
be replaced before the unit is put into operation.
10.1 Regulations for gas connection
Connection flow pressure exceeded
A connection flow pressure above 65 mbar [0.94 psi] will lead to the unit
malfunctioning and the gas components being damaged.
Adhere to the maximum connection flow pressure for natural gas of 21
n
mbar [0.44 psi].
For LPG, adhere to the maximum connection flow pressure of 37 mbar
n
[0.84 psi].
Adhere to the general maximum connection flow pressure of 65 mbar
n
[0.94 psi].
If the pressure is higher, block the gas supply to the unit and do not
n
commission the unit.
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the Natural Gas and
n
Propane Installation Code, CSA B149.1
Requirements for gas type and gas pressure
Check that the factory gas setting on the unit corresponds to the actual local
n
gas supply conditions.
80.06.070_iCombiPro-iCombiClassic_IM_en-GB
10 | Gas connection for gas units
DANGER
NOTICE
screw).
2
83 / 108