Factory Settings And Measured Values - Safety Extra-Low Voltage Test; Factory Settings And Measured Values - Prcd Test; Table 58 Measured Values According To Measuring Specifications - Cable Continuity Test; Table 59 Measured Values According To Measuring Specifications - Safety Extra-Low Voltage Test - Benning ST 755+ Operating Manual

Table of Contents

Advertisement

Appendix
13.4 Factory settings and measured values
Parameter
Measuring range
Resolution
Accuracy
Measuring voltage
Table 58: Measured values according to measuring specifications – Cable continuity test
13.4.6
Factory settings and measured values – Safety extra-
low voltage test
Parameter
Measuring range
Resolution
Accuracy
Table 59: Measured values according to measuring specifications – Safety extra-low voltage test
13.4.7
Factory settings and measured values – PRCD test
Parameter
Tripping current I nom.
Tripping time 1 x I nom.
Tripping time 5 x I nom.
Tripping time ½ x I nom.
Table 60: Factory settings of the limits for PRCD-AC
Parameter
Tripping current I nom.
Tripping time 1 x I nom.
Tripping time 5 x I nom.
Max. contact voltage
Table 61: Factory settings of the limits for PRCD-A und PRCD-F
Parameter
Tripping current I nom.
Tripping time 1 x I nom.
Tripping time 5 x I nom.
Max. contact voltage
Table 62: Factory settings of the limits for PRCD-B und PRCD-B+
Parameter
Tripping current I nom.
Tripping time 1 x I nom.
Tripping time 5 x I nom.
Max. contact voltage
Table 63: Factory settings of the limits for PRCD 2-pin, 3-pin, K, S and S+
Parameter
Testing current
5284 / 08/2023 en
Value
0.05 ... 10 Ω
0.001 Ω
±15 % of the measured value
U
approx. 8 V‑AC
0
Value
1.0 ... 360 V‑DC, 250 V‑AC
0.1 V
±15 % of the measured value
Value
0 ... 100 mA, 100 ... 1 000 mA
BENNING ST 755+ / ST 760+
Value
Unit
30
mA
300
ms
40
ms
300
ms
Value
Unit
42
mA
300
ms
40
ms
35
V
Value
Unit
60
mA
300
ms
40
ms
50
V
Value
Unit
30
mA
300
ms
40
ms
25
V