Testing

9.4 Manual testing

9.4
Manual testing
Manual testing is intended for tests of electrical devices after repair or modification and for
periodic testing.
Requirements
• Please observe the requirements for measuring [} page 71].
• Approved safety measuring lines
Menu
Main menu > VDE 0701, VDE 0702
Main menu > VDE 0751-1
Main menu > VDE 0544-4
Procedure
1. Select the desired test standard in the main menu.
– VDE 0701, VDE 0702
– VDE 0751-1
– VDE 0544-4
2. Select the corresponding protection class of the test sample.
The "Visual inspection" screen with the standard visual inspection is displayed.
3. Carry out a visual inspection.
If you want to carry out the advanced or customer-specific visual inspection, select the
desired visual inspection. To do this, tap the "Visual inspection" line in the upper right of the
screen to open the selection. Tap the desired visual inspection and confirm your selection
with "OK".
The desired visual inspection is displayed. You can adapt it to your needs by showing and
hiding the individual questions and then start the visual inspection.
4. Evaluate the result of the visual inspection [} page 41].
– There are no defects:
Confirm using the button "OK" or "All OK".
If there are no serious defects, tap the "Start" button to complete the visual inspection
and start the test procedure.
– There are defects: Evaluate the defect with the "Error" button or for each negative result
with the "F" button for 'fail' or "N.a." for 'not available'.
If there are serious defects, stop the test. To do this, tap the "Done" button to go directly
to the test report.
5. Select the desired individual test.
Carry out the individual test [} page 79]. To do this, follow the instructions on the display
and the instructions for the respective individual test.
6. Stop the individual test. To do this, tap the "Stop" button.
The result of the individual test is displayed.
7. Tap the "Back" button to go back to the overview of the individual tests.
Tap the "Start" button to carry out the individual test again.
8. Carry out all of the desired individual tests. To do this, follow the steps 5 to 7.
5284 / 08/2023 en