6.2 Binary inputs

Binary objects provide information from the Grundfos booster system.
ID
Object name
BI, 0
Control source status
BI, 2
Rotation status
BI, 3
At minimum speed
BI, 4
At maximum speed
BI, 5
Standby pumps active
BI, 6
Pressure relief active
BI, 7
Soft pressure active
BI, 8
Low-flow boost active
BI, 9
Low-flow stop active
BI, 10
Alternative setpoint active
BI, 11
Digital input 1 status
BI, 12
Digital input 2 status
BI, 13
Digital input 3 status
BI, 14
Digital output 1 status
BI, 15
Digital output 2 status
BI, 16
Subpump 1 presence
BI, 17
Subpump 1 communication status
BI, 18
Subpump 2 presence
BI, 19
Subpump 2 communication status
BI, 20
Subpump 3 presence
BI, 21
Subpump 3 communication status
BI, 22
Subpump 4 presence
BI, 23
Subpump 4 communication status
BI, 24
Subpump 5 presence
R/W
Notes
Status of the actual control source
R
0: Local control
1: Bus control
Rotation status
R
0: No rotation
1: Rotation (one or more pumps running)
0: Not running at minimum speed
R
1: Running at minimum speed
0: Not running at maximum speed
R
1: Running at maximum speed
0: Standby pumps not active
R
1: Standby pumps active
0: Pressure relief not active
R
1: Pressure relief active
0: Soft pressure not active
R
1: Soft pressure active
0: Low-flow boost not active
R
1: Low-flow boost active
0: Low-flow stop not active
R
1: Low-flow stop active
0: Alternative setpoint not active
R
1: Alternative setpoint active
0: Not active
R
1: Active
0: Not active
R
1: Active
0: Not active
R
1: Active
0: Not active
R
1: Active
0: Not active
R
1: Active
0: Subpump not present
R
1: Subpump present
0: Communication OK
R
1: Communication fault
0: Subpump not present
R
1: Subpump present
0: Communication OK
R
1: Communication fault
0: Subpump not present
R
1: Subpump present
0: Communication OK
R
1: Communication fault
0: Subpump not present
R
1: Subpump present
0: Communication OK
R
1: Communication fault
0: Subpump not present
R
1: Subpump present
-
-
-
-
-
-
-
-
-
-
H
-
-
H
H
H
H
H
-
-
-
-
-
-
-
-
-
-
-
-
17