6.3 Binary outputs

Binary objects are used for controlling the Grundfos booster system.
ID
Object name
BO, 0
Set control source
BO, 1
Relay 1 control
BO, 2
Relay 2 control
BO, 4
Reset fault
BO, 5
Fault simulation
BO, 6
Copy settings to local
BO, 7
Relay 3 control
BO, 8
Relay 4 control
BO, 9
Enable max flow limit
H: For MGE model H or newer
For Multi-E with CIM in each pump: always send all commands (writings) to all pumps.
A TPED model H is essentially a Multi-E model H with two pumps.
20
R/W
Notes
It sets the control source.
Set to 1 to enable control via BACnet.
W
0: Local control (default)
1: Bus control
It controls relay 1 if bus control is enabled and relay 1 is
set to be controlled via bus.
W
0: Closed (default)
1: Open
It controls relay 2 if bus control is enabled and relay 2 is
set to be controlled via bus.
W
0: Closed (default)
1: Open
It resets alarm if bus control is enabled.
(It is triggered on rising edge.)
W
0: No resetting (default)
1: Resetting
It enables fault simulation.
W
0: Disabled (default)
1: Enabled
It copies remote settings to local pump settings.
0: Disabled
W
1: Enabled
If enabled, change BO from 0 to "1: Bus control".
It controls relay 3 if bus control is enabled and relay 3 is
set to be controlled via bus.
W
0: Closed (default)
1: Open
It controls relay 4 if bus control is enabled and relay 4 is
set to be controlled via bus.
W
0: Closed (default)
1: Open
It is used to limit the flow.
W
0: No flow limitation
1: Flow limit active
H
-
-
H
H
-
-
H
-
H
-
-
H
H
-
-
H
H
-
-
H
-
-
H