Multistate Inputs - Grundfos CIM 300 BACnet MS/TP Instructions Manual

Hide thumbs Also See for CIM 300 BACnet MS/TP:
Table of Contents

Advertisement

6.4 Multistate inputs

They are objects that contain an enumeration value from the booster system.
ID
Object name
MI, 0
Actual control mode
MI, 1
Actual operating mode
MI, 3
CIM status
MI, 4
Subpump 1 control source
MI, 5
Subpump 2 control source
MI, 6
Subpump 3 control source
MI, 7
Subpump 4 control source
MI, 8
Subpump 5 control source
MI, 9
Subpump 6 control source
R/W
Notes
It reads the current control mode.
1: Constant speed
2: Constant pressure
3: Proportional pressure
4: AUTOADAPT
5: Constant flow
6: Constant temperature
7: Constant level
R
8: Constant percentage (not for MAGNA and MGE)
9: FLOWADAPT
10: Closed-loop sensor control (not for MAGNA and
MGE)
11: Constant diff. pressure
12: Constant diff. temperature
See section Control modes for details on the control
modes.
It reads the current operating mode.
1: Start (normal)
R
2: Stop
3: Minimum
4: Maximum
It reads the status of the CIM module, thus is useful
for fault finding.
1: OK
R
2: EEPROM fault
3: Memory fault
1: Buttons
2: GENIbus
R
3: GENIlink
4: External control
1: Buttons
2: GENIbus
R
3: GENIlink
4: External control
1: Buttons
2: GENIbus
R
3: GENIlink
4: External control
1: Buttons
2: GENIbus
R
3: GENIlink
4: External control
1: Buttons
2: GENIbus
R
3: GENIlink
4: External control
1: Buttons
2: GENIbus
R
3: GENIlink
4: External control
-
H
-
H
-
H
-
H
-
-
H
-
-
H
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ciu 300 bacnet ms/tpCiu 500 bacnet ipCim 500 bacnet ip