Illustration of closed-loop control Alarms and warnings 1.2 Notes Static status parameters, input assembly 3 The symbols and notes below may appear in Grundfos Measured parameters, input assembly 4 installation and operating instructions, safety instructions and Sensor-dependent measurements service instructions.
3. System description The system diagrams give an overview of how to connect CIM/ 2.4 Definitions and abbreviations CIU 500 to the Grundfos E-pump that is to be connected to a EtherNet/IP network. Address Resolution Protocol. Translates IP addresses into MAC-addresses.
Conductors: A, B and Y. CIU box enclosure class IP54 CIU box dimensions (H x W x D) 182 x 108 x 82 mm 4.2 CIM 500 Ethernet CIM 500 Ethernet specifications Description Comments DHCP, HTTP, Ping, FTP, SMTP, SNTP,...
5.3 Setting the IP addresses The CIM 500 Ethernet module is by default set to a fixed IP address. It is possible to change the IP address settings from the built-in webserver.
Industrial Ethernet protocol is active. Green on Ethernet link on the RJ45 connector is OK. 5.5 Status LEDs The CIM 500 Ethernet module has two Status LEDs, LED1 and LED2. See fig. 4. • Red and green status LED, LED1, for Ethernet communication •...
6.2 Control parameters, output assembly 11 Table legend CUE: Pumps with CUE drive only. MGE: Pumps with MGE motor only. H: Only available on model H and later versions. S: Sensor required. ●: Always available. *: If the E-pump is a TPE3 or a TPE Series 2000, the value is estimated and always available. Range/ Name Data type...
Page 10
SetRelayOutput 1-4 6.2.2 Explanation to control bits This module can control the electromechanical relays in the E- pump if they are configured via a Grundfos PC Tool to be bus- SetRemoteLocal controlled. Control bit for setting the E-pump in remote mode (controlled from the bus), or in local mode (controlled from the operating Only available for MGE and CUE based pumps.
Page 11
6.2.3 Explanation to control mode SetControlMode Control enumeration for selection of the remote control mode. Control modes Description Illustration The setpoint of the E-pump is a percentage of the maximum > ConstSpeed (0) performance. > ConstFreq (1) No sensor is required, and in these modes the E-pump is operating in open-loop control.
Page 12
[%] × (r [unit] = X ) + r The actual setpoint, whether it has been set via Grundfos GO [%] × (10 m – 1 m) + 1 m Remote, the pump display, the pump buttons or the fieldbus, can [%] ×...
6.3 Configuration parameters, Input/Output explicit messaging Use this output parameter to adjust the maximum flow limit of the pump. The pump flow will be limited by the maximum flow limit in any control mode if the FLOW function has been enabled on the pump. LIMIT Only MAGNA3, TPE series 2000 and TPE3 support the FLOW function.
Page 14
Range/ Name Data type Scaling Description Resolution ControlMode Present status of Control mode ● ● ● OperatingMode Present status of Operating mode ● ● ● ● ● ● AlarmCode Alarm code ● ● ● WarningCode Warning code Feedback sensor unit Enum 0-255 0: bar...
Page 15
Only available on MAGNA3 and MGE model H and later. The E-pump is controlled from a local source, buttons or No setpoint influence Grundfos GO Remote or from an external digital input The setpoint is influenced The E-pump is controlled from EtherNet/IP, remotely...
6.5 Illustration of closed-loop control SetSetpoint (output) Setpoint UserSetpoint ActualSetpoint Closed-loop Motor with Pump and Speed Frequency influence control frequency hydraulic converter system SystemFeedback Sensor Feedback sensor value Fig. 10 Illustration of closed-loop control and the associated data parameters SystemFeedback In closed-loop control, this is the value of the controlled system variable (feedback/primary sensor).
6.6 Alarms and warnings Code Alarm and warning description Electronic inverter protection activated (EIP) Parameter Name Description Motor bearing temperature high (Pt100) in drive end AlarmCode Code for E-pump alarm. (DE) WarningCode Code for E-pump warning. Motor bearing temperature high (Pt100) in non-drive In the AlarmCode parameter, the cause of an E-pump alarm can end (NDE) be read.
6.7 Static status parameters, input assembly 3 Static status parameters are parameters that describe characteristics of the E-pump. They are constants unable to change. This assembly is included in assembly 1. Table legend ●: Always available. Range/ Name Data type Scaling Description Resolution...
CUE: Pumps with CUE drive only. 6.8 Measured parameters, input assembly 4 MGE: Pumps with MGE motor only. Measured parameters are physical values measured by internal and external sensors and values calculated by the E-pump itself G: Only available on model G and later versions. based on measured values and its state/mode behaviour.
Page 20
Remote differential temperature RemoteDiffTemp (parameter 316). • FluidTemperature (parameter 318) measured by a built-in Grundfos sensor and RemoteTemperature2 (parameter 315) measured by an analog or temperature input. • RemoteTemperature1 (parameter 314) and RemoteTemperature2 (parameter 315) measured by an analog or temperature input.
Connection of a pressure sensor and selection of the analog input function "Constant pressure control" will make RemotePressure1 measurement available. CUE and all E-pump types except model H and later. EtherNet/IP data parameter generated from sensor measurement Sensor unit configuration with Grundfos GO Remote Feedback sensor (AI1) Measuring sensor* (AI2) Measuring sensor** (AI3) mbar...
E-pump model H and later Analog Measured parameters Temperature Grundfos Grundfos input Mapped to EtherNet/IP data Selected from Grundfos GO Pt100 built-in LiqTec AI1, AI2, parameter Remote display input T1, T2 sensor sensor Pump inlet pressure ● InletPressure (306) Pump inlet diff. press.
You can detect faults in a module by observing the status of the two status LEDs. See the table below. CIM 500 fitted in a Grundfos product or CIM 500 fitted in a CIU 500 Ensure that SW1 is in position "3".
Page 24
10. Grundfos alarm and warning codes This is a complete list of alarm and warning codes for Grundfos products. For the codes supported by this product, see the alarms and warnings section. Code Description Code Description Code Description Outlet valve...
Page 25
Code Description Code Description Code Description Electronic inverter protection Signal fault, temperature sensor 3 activated (EIP) (t_mo3) Signal fault, Smart trim gap sensor Signal fault, vibration sensor Signal fault, bearing temperature Motor temperature 3 (Pt100, sensor (Pt100), general or top t_mo3) bearing Bearing temperature high (Pt100),...
Page 26
Code Description Code Description Code Description Low pressure Communication fault, I/O module Motor phase failure Diaphragm tank precharge Automatic motor model recognition Combi event pressure out of range failed Motor relay has been forced VFD not ready Night flow max. limit exceeded (manually operated or commanded) Water shortage, level 2...
Page 27
Appendix 1. Webserver configuration The built-in webserver offers easy monitoring of the CIM 500 module, and makes it possible to configure the selected Industrial Ethernet protocol. Using the webserver, you can also update the firmware of the CIM 500 module and store or restore settings, among other functions.
Page 28
Description Enter username. Username Default: admin. Enter password. Default: Grundfos. After the first login, you are forced to change the password. The password must contain: • at least 8 and maximum 20 characters • at least one lower case letter Password •...
Page 29
(for example PLC program) before installing the device. To enable product simulation, select a product type from the dropdown list. To terminate product simulation, select "No Simulation". You need a contract with Grundfos and an external router with Internet connection to gain access to the GRM server.
Page 30
1.5 Network settings This web page is used to configure the network settings of the webserver and of the GENIpro TCP protocol. The network settings here are also used for BACnet IP. Additional configuration of BACnet IP is done in the Real Time Ethernet Protocol menu. See EtherNet/IP configuration.
Page 31
1.6 User Management A login is required for any change of the CIM 500 settings, and this web page is used to configure the username and password. See Login. It is only possible to configure one user. User management Fig. 5...
Page 32
1.7 Update You can update the firmware by means of the built-in webserver. The binary file is supplied by Grundfos. To make installation and configuration easier, you can upload the configuration to a PC for backup or distribution to multiple modules.
Page 33