5. Supported services

BACnet Interoperability Building Blocks (BIBBs) are collections of one or more BACnet services. These are described in terms of an "A" and a
"B" device. Both devices are nodes on a BACnet inter-network. In most cases, the "A" device acts as the user of data (client), and the "B"
device is the provider of this data (server).
The CIM/CIU 300 and 500 are BACnet Application-Specific Controllers (B-ASC) with a few additional services.

5.1 Data-sharing services

Name
ReadProperty
ReadPropertyMultiple
WriteProperty
WritePropertyMultiple
SubscribeCOV
ConfirmedCOVNotification
UnconfirmedCOVNotification

5.2 Device management services

Name
Who-Is
I-Am
Who-Is
I-Am
Who-Has
I-Have
DeviceCommunicationControl
BACnet BIBB code
Notes
DS-RP-B
The CIM 300 and 500 can be provider of data.
The CIM 300 and 500 can be provider of data and return multiple
DS-RPM-B
values at one time.
DS-WP-B
The CIM 300 and 500 allow a value to be changed over the network.
The CIM 300 and 500 allow multiple values to be changed over the
DS-WPM-B
network.
The CIM 300 and 500 can be provider of "Change Of Value" data.
DS-COV-B
Both support up to 10 simultaneous COV subscriptions. Subscription
lifetime can be limited or unlimited.
BACnet BIBB code
Notes
The CIM 300 and 500 can seek information about device attributes
DM-DDB-A
of other devices and interpret device announcements.
The CIM 300 and 500 can provide information about their device
DM-DDB-B
attributes and respond to requests to identify themselves.
The CIM 300 and 500 can provide address information about their
DM-DOB-B
objects upon request.
The CIM 300 and 500 can respond to communication control
DM-DCC-B
requests. They support both limited and unlimited duration. The
password, if required, is "Grundfos".