4.2 Setting the industrial Ethernet protocol

The CIM 500 Ethernet module has a rotary switch for selecting
industrial Ethernet protocol.
Selecting the industrial Ethernet protocol
Pos.
Description
0
PROFINET IO (default)
1
Modbus TCP
2
BACnet IP
3
EtherNet/IP
4
GRM IP (requires a contract with Grundfos)
5.E
Reserved - LED1 being permanently red: invalid configuration
Reset to factory default
Note: The rotary switch must be set in this position for 20 seconds
F
to reset to factory default. During this period, LED1 flashes red and
green at the same time to indicate a reset.
Every change of the rotary switch while the module is
powered on causes the module to restart.
Related information
3.7 Selecting the BACnet MAC address

4.3 Setting the IP addresses

By default, the CIM 500 Ethernet module is set to a fixed IP
address. You can change the IP address settings from the built-in
webserver.
IP address:
Default IP settings used
Subnet mask:
by the webserver
Gateway:
IP settings for BACnet IP
To be set via the webserver

4.4 Establishing connection to the webserver

You can configure the CIM 500 using the built-in webserver. To
establish a connection from a PC to the CIM 500, the following
steps are required:
Connect the PC and the CIM 500 using an Ethernet cable.
Configure the PC Ethernet port to the same subnetwork as that
of the CIM 500, for example, 192.168.1.101, and the subnet
mask to 255.255.255.0.
Open a standard internet browser and type 192.168.1.100 in the
URL field.
Log in to the webserver:
User
admin (default)
Password
Grundfos (default)
The user name and password may have been changed
from their default values.
Change the username and password at the first login.
CIM 500 connected to PC via Ethernet cable
For further information on how to use the webserver, see
section Webserver configuration.
You can use both ETH1 and ETH2 to establish a
connection to the webserver.
You can access the webserver while the selected
industrial Ethernet protocol is active.
Related information
A.1.2. How to configure an IP address on your PC using Windows
10
A.1.1. Webserver configuration
192.168.1.100
255.255.255.0
192.168.1.1