GRUNDFOS INSTRUCTIONS
PROFIBUS and PROFINET for
Grundfos boosters
CIM/CIU 150 PROFIBUS DP
CIM/CIU 500 Ethernet for PROFINET IO
Functional profile and user manual
Pumpland.ru

Advertisement

Table of Contents
loading

Summary of Contents for Grundfos CIM 150 PROFIBUS DP

  • Page 1 GRUNDFOS INSTRUCTIONS PROFIBUS and PROFINET for Grundfos boosters CIM/CIU 150 PROFIBUS DP CIM/CIU 500 Ethernet for PROFINET IO Functional profile and user manual Pumpland.ru...
  • Page 2: Table Of Contents

    PROFINET IO, CIM 500 setup Connecting the ethernet cable 1.2 Notes Setting the Industrial Ethernet protocol The symbols and notes below may appear in Grundfos Setting the IP addresses installation and operating instructions, safety instructions and Establish a connection to the webserver service instructions.
  • Page 3: Introduction

    Grundfos GO control Grundfos products via infrared or 2.1 About this functional profile Remote radio communication. Available for iOS This functional profile describes these protocols for the Grundfos and Android devices. booster systems mentioned below: Head (pressure). • CIM/CIU 150 PROFIBUS DP Hyper Text Transfer Protocol.
  • Page 4: System Description

    The system diagrams give an overview for the different GENIbus technologies of how to connect the module or unit to the RS-485 PROFIBUS DP Grundfos booster system that you connect to a PROFIBUS/ CRE with PROFINET network. Hydro Multi-E add-on...
  • Page 5: Profinet Io, Cim 500

    Example of a CIU 500 solution for Hydro Multi-E, Fig. 5 model G CIM 500 PROFIBUS DP Example of a CIM 500 solution for Hydro Multi-E Fig. 6 model H and later. Pumps connected via built-in radio communication (Grundfos Glowpan) Pumpland.ru...
  • Page 6: Specifications

    182 x 108 x 82 mm 4.2 CIM 150 PROFIBUS DP The table below provides an overview of the specifications for Grundfos CIM 150 and CIU 150. For further details, please refer to the specific sections of this functional profile. PROFIBUS DP specifications...
  • Page 7: Profibus Dp, Cim 150 Setup

    Red and green status LED for LED1 PROFIBUS communication Red and green status LED for GENIbus communication between LED2 CIM/CIU 150 and the Grundfos product Hexadecimal rotary switch for setting the PROFIBUS address, four most significant bits Hexadecimal rotary switch for setting...
  • Page 8: Setting The Profibus Address

    Off. CIM 150 is switched off. GENIbus communication between CIM Permanently green. 150 and the Grundfos product is OK. CIM 150 does not support the connected A restart of CIM/CIU 150 has to be performed for a PROFIBUS Permanently red.
  • Page 9: Profinet Io, Cim 500 Setup

    Each ethernet port has its own MAC address. Modbus TCP BACnet IP Ethernet switch EtherNet/IP GRM IP (requires a contract with Grundfos) CIM 500 CIM 500 CIM 500 Reserved, LED1 will be permanently red to indicate an 5..E invalid configuration...
  • Page 10: Establish A Connection To The Webserver

    Configure the PC ethernet port to the same subnetwork as 500 and the Grundfos product. CIM 500, for example 192.168.1.101, and the subnet mask to CIM 500 does not support the Grundfos Permanently red 255.255.255.0. See section A.2 Webserver configuration product connected.
  • Page 11: Detailed Description Of Data Modules

    7.1 Data types TPED, MAGNA3-D: Percentage of the setpoint range. Grundfos CIU 150 and CIU 500 support the following data types. Open loop: All data types, except for data type 10, comply with specification MPC, Multi-E: Percentage of the maximum performance.
  • Page 12 7.2.3 Explanation to control mode Control enumeration for selection of the remote control mode. Control modes Description Illustration The setpoint of the booster system is a percentage of the maximum performance. > ConstSpeed (0) No sensor is required, and in these modes the booster >...
  • Page 13 This is the normal mode. The booster system is controlled UserSetpoint with the same scaling. according to the selected control mode and setpoint. The actual setpoint, whether it has been set via Grundfos GO See section 7.2.3 Explanation to control mode.
  • Page 14: Status Module (Statusmodule, Module 1)

    CopyToLocal (Module 2, byte 1, bit 4) to value ‘1’ in both The actual setpoint, whether it has been set via Grundfos GO pumps. Any writings to the control module (module 2) must be Remote, the pump or controller display or buttons, or the fieldbus, written to each pump.
  • Page 15 Operating mode and setpoint. This bit is not supported by Multi-E model G and earlier models. The booster system is controlled from a local source, display or Grundfos GO Remote, or from an external 0: Copy of remote settings to local settings is not active. digital input.
  • Page 16: Illustration Of Closed-Loop Control

    7.4 Illustration of closed-loop control Setpoint (output) UserSetpoint ActualSetpoint Setpoint RelativePerformance Closed-loop Hydraulic influence control system ProcessFeedback Sensor Feedback/primary sensor value Fig. 21 Illustration of closed-loop control, see also page 7.5 Direct bus control of pumps (ControlPumps, module 50) This module is only available for CU 352. With this module it is possible to individually force each of the six zone pumps, the pilot pump and the backup pump to stop.
  • Page 17: Alarms And Warnings

    7.7 Alarms and warnings Module Name Description WarningCode Code for booster system warning. FaultCode Code for booster system alarm. In the WarningCode module, the cause of a booster system warning can be read. A warning has no influence on the booster system operation.
  • Page 18: Measurement Modules

    This is measurement data that can be read in Hydro MPC, Control MPC and Hydro Multi-E. PROFIBUS/PROFINET direction: Inputs. Data Module Name Unit Description type The Grundfos-specific warning code. WarningCode For a list of warning codes. See section ● ● ● 7.7 Alarms and warnings.
  • Page 19 Data Module Name Unit Description type Indicates active system functions. 0: - 1: Emergency run function 2: Standby pumps 3: Pump test run 4: Alternative setpoint 5: Clock program SystemActiveFunctions Bits 6: Remote VNC (Virtual Network Connection) ● 7: Remote bus 8: Remote service port 9: Pressure-relief function 10: Soft-pressure function...
  • Page 20 Data Module Name Unit Description type One bit for each pump indicating that there is no communication with the pump. Logical "1": No communication with the pump. 0: Communication fault, zone pump 1 1: Communication fault, zone pump 2 PumpsCommFault Bits 2: Communication fault, zone pump 3 ●...
  • Page 21 The table below shows the relation between the Hydro Multi-E PROFIBUS/PROFINET measurement modules and the measurement unit selected with Grundfos GO Remote for the feedback sensor. Only one of the measurement module groups in the table below is available at a time.
  • Page 22: Zone Pump Modules

    Description Thermal relay 2 in motor, for example thermistor Zone pump control: Hardware fault, type 1 0:Local (buttons on Hardware shutdown (HSD) pump, Grundfos GO Internal communication fault AccessMode* Remote or external Communication fault, twin-head pump digital input). 1:Controlled from Hardware fault, type 2 booster system.
  • Page 23: Zone Pump Extension Modules

    Byte 10 ControlSource system) (data type 5) [enum] 3: GENIlink (Grundfos GO Remote) 4: External digital control. 7.11 Pilot pump module (PilotPumpModule, module This module is available for CU 352 only. A pilot pump module is only available for Hydro MPC-E and only if the pilot pump is an E-pump.
  • Page 24: Device Identification (Deviceidentification, Module 47)

    30: Smart Digital Dosing, DDA 1: Smart Digital Dosing, DDA 1: With 3-phase pumps 39: Hydro Multi-E model H and later 2: With 1-phase pumps UnitType [enumeration] According to description above. UnitVersion [enumeration] Used by Grundfos. CIMSoftwareVersion [number] CIMSoftwareRevision [number] CIMModel [enumeration] Pumpland.ru...
  • Page 25: Product Simulation

    8. Product simulation The CIM module can be put in product simulation mode in which case it will generate life-like simulated values of all the PROFIBUS/PROFINET input data modules. It will thus be possible to connect a PROFIBUS/PROFINET master to CIU 150 or CIU 500 without this device being connected to a real pump in a real-life system.
  • Page 26: Fault Finding The Product

    You can detect faults in a CIM 150 PROFIBUS module by observing the status of the two communication LEDs. See the table below. 9.1.1 LED status CIM 150 fitted in a Grundfos booster system Fault (LED status) Possible cause Remedy 1.
  • Page 27: Cim/Ciu 500

    CIM 500 does not support the Grundfos Contact the nearest Grundfos company. permanently red. product connected. 5. PROFINET IO LED1 is permanently red. a) Connected Grundfos product is not Contact the nearest Grundfos company. supported. b) Illegal position of protocol switch, SW1 Check that the rotary switch SW1 is set to "0".
  • Page 28: Profibus Address

    11. Disposal This product or parts of it must be disposed of in an environmentally sound way: 1. Use the public or private waste collection service. 2. If this is not possible, contact the nearest Grundfos company or service workshop. Pumpland.ru...
  • Page 29 12. Grundfos alarm and warning codes This is a complete list of alarm and warning codes for Grundfos products. For the codes supported by this product, see the alarms and warnings section. Code Description Code Description Code Description Outlet valve...
  • Page 30 Code Description Code Description Code Description Electronic inverter protection Signal fault, temperature sensor 3 activated (EIP) (t_mo3) Signal fault, Smart trim gap sensor Signal fault, vibration sensor Signal fault, bearing temperature Motor temperature 3 (Pt100, sensor (Pt100), general or top t_mo3) bearing Bearing temperature high (Pt100),...
  • Page 31 Code Description Code Description Code Description Low pressure Communication fault, I/O module Motor phase failure Diaphragm tank precharge Automatic motor model recognition Combi event pressure out of range failed Motor relay has been forced VFD not ready Night flow max. limit exceeded (manually operated or commanded) Water shortage, level 2...
  • Page 32 Appendix The appendix describes the parts of the CIM 500 webserver needed for the configuration of a PROFINET IO ethernet connection. For other CIM 500 webserver features, not specifically related to PROFINET IO, see the installation and operating instructions for CIM 500. A.1 How to configure an IP address on your PC For connecting a PC to CIM 500 via ethernet, the PC must be set to use a fixed (static) IP address belonging to the same...
  • Page 33 Fig. 2 User name Enter user name. Default: admin. Password Enter password. Default: Grundfos. The user name and password can be changed on the webserver under "User Management". A.4 PROFINET IO configuration This web page is used to configure all the parameters relevant to the PROFINET IO protocol standard.
  • Page 34 Pumpland.ru...
  • Page 35 Norway Turkey Av. Humberto de Alencar Castelo Branco, Siu Wai Industrial Centre GRUNDFOS Pumper A/S GRUNDFOS POMPA San. ve Tic. Ltd. Sti. 29-33 Wing Hong Street & Strømsveien 344 Gebze Organize Sanayi Bölgesi CEP 09850 - 300 68 King Lam Street, Cheung Sha Wan...
  • Page 36 96846340 0418 ECM: 1222615 www.grundfos.com Pumpland.ru...