Cim/Ciu 500 Bacnet Ip - Grundfos CIM 300 BACnet MS/TP Instructions Manual

Hide thumbs Also See for CIM 300 BACnet MS/TP:
Table of Contents

Advertisement

9.1.2.2 The booster system does not react to control commands from the bus.
Cause
The booster system is running in local mode.
9.1.2.3 There are only a few BACnet objects available, and the GENIbus LED flashes red.
Cause
There is no communication between the CIM/CIU and the booster
system.
Related information
3.3 Connecting to the BACnet network
3.4 Setting the BACnet transmission speed
3.5 Selecting the Device Object Instance Number
3.7 Selecting the BACnet MAC address
3.8 Termination resistor

9.2 CIM/CIU 500 BACnet IP

You can detect faults in CIM/CIU 500 by observing the status of the two communication LEDs.
9.2.1 LED status: The CIU 500 is fitted in a Grundfos booster system.
9.2.1.1 Both LEDs remain off when the power supply is connected.
Cause
The CIM/CIU is fitted incorrectly in the connected Grundfos product.
The CIM/CIU is defective.
9.2.1.2 The LED2 for internal communication is flashing red.
Cause
There is no internal communication between the CIM/CIU and the
connected Grundfos product.
9.2.1.3 The LED2 for internal communication is permanently red.
Cause
The CIM/CIU does not support the connected Grundfos product.
9.2.1.4 The LED1 for BACnet communication is permanently red.
Cause
There is fault in the CIM 500 BACnet IP configuration.
9.2.1.5 The LED1 is permanently red and green at the same time.
Cause
There is error in the firmware download.
9.2.1.6 The LED2 is permanently red and green at the same time.
Cause
There is a memory fault.
Related information
4. BACnet IP, CIM 500 setup
9.2.2 LED status: The CIM 500 is fitted in the CIU 500.
9.2.2.1 Both LEDs remain off when the power supply is connected.
Cause
The CIM/CIU is defective.
38
Remedy
Set the booster system to bus control by setting the Present_Value
of BO 0 to 1.
Set bus control on the CU 35X display. Select "Settings" >
"Secondary functions" > "Control source", and select "Controlled
from bus".
Remedy
Make sure that the GENIbus cable between the CIM/CIU 300 and
the booster system is connected correctly.
Make sure that the booster system is switched on and able to
communicate on the GENIbus.
Remedy
Ensure that the CIM/CIU is fitted and connected correctly.
Replace the CIM/CIU.
Remedy
Make sure that the CIM/CIU is fitted correctly in the Grundfos
product.
Remedy
Contact the nearest Grundfos company.
Remedy
Make sure that the rotary switch SW1 is set to 2.
Make sure that BACnet IP address configuration is correct.
Remedy
Use the webserver to download the firmware again.
Remedy
Replace the CIM/CIU.
Remedy
Replace the CIM/CIU.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ciu 300 bacnet ms/tpCiu 500 bacnet ipCim 500 bacnet ip

Table of Contents