Analog Outputs - Grundfos CIM 300 BACnet MS/TP Instructions Manual

Hide thumbs Also See for CIM 300 BACnet MS/TP:
Table of Contents

Advertisement

Related information
7.7 Tank-filling applications
12. Grundfos alarm and warning codes

6.7 Analog outputs

Object for setting a new setpoint in the booster system.
ID
Object name
AO, 0
Set setpoint
AO, 1
Tank-filling start limit
AO, 2
Tank-filling stop limit
AO, 3
Tank-filling alarm high-limit
AO, 4
Tank-filling warning low-limit
AO, 5
Set max. flow limit
AO, 6
Set speed setpoint Pump1
AO, 7
Set speed setpoint Pump2
AO, 8
Set speed setpoint Pump3
AO, 9
Set speed setpoint Pump4
AO, 10
Set speed setpoint Pump5
AO, 11
Set speed setpoint Pump6
AO, 12
Set speed setpoint Pilot Pump
Set speed setpoint Backup
AO, 13
Pump
H: For MGE model H or newer
For Multi-E with CIM in each pump, always send all commands (writings) to all pumps.
A TPED model H is essentially a Multi-E model H with two pumps.
Related information
7.2 Setpoint
28
R/W
Notes
Sets the booster system setpoint if bus control is
W
enabled. A value of 0 does not imply a stop. See section
Setpoint.
W
Sets the start limit in percentage of tank height.
W
Sets the stop limit in percentage of tank height.
W
Sets the alarm high-limit in percentage of tank height.
W
Sets the warning low-limit in percentage of tank height.
W
Sets the maximum flow limit value.
Sets the man speed setpoint pump1 if man start is
W
enabled.
Sets the man speed setpoint pump2 if man start is
W
enabled.
Sets the man speed setpoint pump3 if man start is
W
enabled.
Sets the man speed setpoint pump4 if man start is
W
enabled.
Sets the man speed setpoint pump5 if man start is
W
enabled.
Sets the man speed setpoint pump6 if man start is
W
enabled.
Sets the man speed setpoint pump1 if man start is
W
enabled.
Sets the man speed setpoint pump1 if man start is
W
enabled.
Unit
%
%
-
-
%
-
-
%
-
-
%
-
-
3
-
-
m
/h
%
-
-
%
-
-
%
-
-
%
-
-
%
-
-
%
-
-
%
-
-
%
-
-
-
-
-
-
H
-
-
-
-
-
-
-
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ciu 300 bacnet ms/tpCiu 500 bacnet ipCim 500 bacnet ip

Table of Contents