Specifications - Grundfos CIM 300 BACnet MS/TP Instructions Manual

Hide thumbs Also See for CIM 300 BACnet MS/TP:
Table of Contents

Advertisement

2.5 Specifications

The table below provides an overview of the specifications for the Grundfos CIM/CIU 300 for BACnet MS/TP and the CIM/CIU 500 for BACnet
IP. For further details, refer to the specific sections of this functional profile.
General data
Ambient humidity
Operating temperature
Storage temperature
GENIbus visual diagnostics
BACnet MS/TP
BACnet connector
BACnet connection type
BACnet wire configuration
Maximum cable length [m]
Recommended cross-section of BACnet cable
MAC address
Line termination
Supported transmission speeds [bit/s]
Data bits
Stop bits
Parity
BACnet visual diagnostics
Maximum number of BACnet devices
Grundfos BACnet vendor ID
BACnet segmentation support
Character set support
BACnet device profile
BACnet MS/TP master
Manual slave address binding
BACnet protocol revision
BACnet IP
Application layer
Transport layer
Internet layer
Link layer
Ethernet cable
Maximum cable length
Transmission speed
Industrial Ethernet protocols
BACnet protocol revision
CIM 300 and 500
Dimensions [w x h x d] [mm]
Power supply
Connection to booster system
CIU 300 and 500
CIU box dimensions (H x W x D)
Power supply
GENIbus connection type
Enclosure class
Recommended cross-section of GENIbus cable
Description
30-95 %
-20 to +45 °C
-25 to +70 °C
LED2
Description
Screw-type terminal
RS-485
2-wire + ground
1200
2
0.20 - 0.25 mm
0-127
On or Off
9600, 19200, 38400, 76800
8
1
None
LED1
32
227
No
ANSI X3.4 and UTF8
B-ASC
Yes
No
For hardware version R4: 4
For hardware version R8: 9
Description
DHCP, HTTP, Ping, FTP, SMTP, SNTP,
BACnet IP
UDP
Internet protocol V4 (IPv4)
ARP, media access control (Ethernet)
CAT5, CAT5e or CAT6
100 metres at 10/100 Mbit/s
10 Mbit/s, 100 Mbit/s
PROFINET IO, Modbus TCP, BACnet IP
etc.
9
Description
50 x 19 x 80
10-pin connection
Description
182 x 108 x 82 mm
24-240 V AC/DC
RS-485, 3-wire + screen
IP54
2
0.20 - 0.25 mm
Comments
It is considered relative, non-condensing.
The LED is in one of the following states:
Off, permanently green, flashing red, permanently red.
Comments
3 pins
Conductors: Plus, Minus and Ground
Equals 4000 ft
AWG24 or AWG23
To be set via rotary switches SW6 and SW7
To be set via DIP switches SW1 and SW2
To be set via DIP switches SW4 and SW5
Fixed value
Fixed value
Fixed value
Red and green status LED
Number can be increased by using repeaters
Supported character sets
BACnet Application-Specific Controller
CIM/CIU 300 is a BACnet MS/TP master device
Comments
Rotary switch in position 2
Supports auto cable-crossover detecting (Auto-MDIX)
Corresponds to 328 feet
Auto-detected
Selected with rotary switch
Comments
Supplied by the booster system
Comments
Located in the unit
Conductors: A, B and Y
AWG24 or AWG23
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ciu 300 bacnet ms/tpCiu 500 bacnet ipCim 500 bacnet ip

Table of Contents