6.5 Multistate outputs

They are objects that set an enumeration value in the booster system.
ID
Object name
MO, 0
Set control mode
MO, 1
Set operating mode
MO, 2
Product simulation
MO, 3
Control subpump 1
MO, 4
Control subpump 2
MO, 5
Control subpump 3
MO, 6
Control subpump 4
R/W
Notes
It sets the control mode if bus control is enabled.
1: Constant speed (default)
2: Constant pressure
3: Proportional pressure
4: AUTOADAPT
5: Constant flow
6: Constant temperature
W
7: Constant level
8: Constant percentage (not for MAGNA and MGE)
9: FLOWADAPT
10: Closed-loop sensor control (not for MAGNA and MGE)
11: Constant diff. pressure
12: Constant diff. temperature
See section Control modes for details on the control
modes.
It sets the operating mode if bus control is enabled.
1: Start (normal)
W
2: Stop (default)
3: Minimum
4: Maximum (Hydro MPC and Hydro Multi-E only)
It enables product simulation for commissioning and
testing purposes It can only be enabled when no physical
booster system is present.
1: Disabled
5: Hydro Multi-E (Model G and earlier)
W
6: Hydro MPC
7: Hydro Multi-B
10: Hydro Multi-E (MGE model H/I)
See section Product simulation for details.
Manual control of subpump 1
1: Automatic control (default)
W
2: Forced start (MPC only)
3: Forced stop
Manual control of subpump 2
1: Automatic control (default)
W
2: Forced start (MPC only)
3: Forced stop
Manual control of subpump 3
1: Automatic control (default)
W
2: Forced start (MPC only)
3: Forced stop
Manual control of subpump 4
1: Automatic control (default)
W
2: Forced start (MPC only)
3: Forced stop
-
H
-
-
-
-
-
-
-
-
-
23