Bacnet Ip, Cim 500 Setup; Connecting The Ethernet Cable - Grundfos CIM 300 BACnet MS/TP Instructions Manual

Hide thumbs Also See for CIM 300 BACnet MS/TP:
Table of Contents

Advertisement

4. BACnet IP, CIM 500 setup

WARNING
Electric shock
Death or serious personal injury
Connect the CIM 500 only to SELV circuit.

4.1 Connecting the Ethernet cable

Use RJ45 plugs and Ethernet cable. Connect the cable shield to
protective earth at both ends.
It is important to connect the cable shield to earth through
an earth clamp or to connect the cable shield to earth in
the connector.
Maximum cable length
Speed
Cable type
[Mbit/s]
10
CAT5
100
CAT5e, CAT6
The CIM 500 is designed for flexible network installation. The built-
in two-port switch makes it possible to daisy chain from product to
product without additional Ethernet switches. The last product in the
chain is only connected to one of the Ethernet ports. Each Ethernet
port has its own MAC address.
1
CIM
500
CIM
500
Example of Industrial Ethernet network
Pos.
Description
1
Ethernet switch
12
Maximum cable length
[m/ft]
100/328
100/328
CIM
CIM
500
500
5
4
1
Example of Ethernet connection
Pos.
Description
1
Industrial Ethernet RJ45 connector 1
2
Industrial Ethernet RJ45 connector 2
3
Rotary switch for protocol selection
4
Data activity LED for connector 1
5
Link LED for connector 1
6
Data activity LED for connector 2
7
Link LED for connector 2
Green and red status LED for Ethernet
8
communication
Green and red status LED for internal
9
communication between the module and the
booster system
6
7
3
2
8
9
Designation
ETH1
ETH2
SW1
DATA1
LINK1
DATA2
LINK2
LED1
LED2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ciu 300 bacnet ms/tpCiu 500 bacnet ipCim 500 bacnet ip

Table of Contents