Analog Inputs - Grundfos CIM 300 BACnet MS/TP Instructions Manual

Hide thumbs Also See for CIM 300 BACnet MS/TP:
Table of Contents

Advertisement

6.6 Analog inputs

They are objects with measured values and status information from the booster system.
ID
Object name
AI, 0
Fault code
AI, 1
Warning code
AI, 3
Capacity
AI, 4
Head
AI, 5
Flow
AI, 6
Relative performance
AI, 9
Actual setpoint
AI, 13
Power
AI, 15
Inlet pressure
AI, 16
Remote pressure
AI, 20
Remote temperature
AI, 22
Fluid temperature
AI, 25
Auxiliary sensor input
AI, 26
Specific energy
AI, 27
Runtime
AI, 30
Energy consumption
AI, 33
Ambient temperature
AI, 34
Forward temperature
AI, 35
Return temperature
AI, 36
Differential temperature
AI, 37
Outlet pressure
AI, 38
Feed tank level
AI, 39
Subpump 1 fault code
AI, 40
Subpump 1 runtime
AI, 41
Subpump 1 speed
AI, 42
Subpump 2 fault code
AI, 43
Subpump 2 runtime
AI, 44
Subpump 2 speed
AI, 45
Subpump 3 fault code
AI, 46
Subpump 3 runtime
AI, 47
Subpump 3 speed
AI, 48
Subpump 4 fault code
AI, 49
Subpump 4 runtime
AI, 50
Subpump 4 speed
AI, 51
Subpump 5 fault code
AI, 52
Subpump 5 runtime
AI, 53
Subpump 5 speed
AI, 54
Subpump 6 fault code
AI, 55
Subpump 6 runtime
AI, 56
Subpump 6 speed
AI, 57
Remote temperature 2
AI, 58
User setpoint
AI, 59
Analogue influence
R/W
Notes
Grundfos fault code
R
See section Grundfos alarm and warning codes.
Grundfos warning code.
R
See section Grundfos alarm and warning codes.
R
Actual capacity value (process feedback)
R
Actual system head/pressure
R
Actual system flow
R
Performance relative to maximum performance
R
Actual setpoint
R
Total power consumption of the system
R
System inlet pressure
R
Measured pressure at external sensor
R
Temperature at external sensor
R
Liquid temperature
R
Auxiliary sensor input
R
Specific energy of the system
R
Total operating time of the system
R
Total energy consumption of the system
R
Ambient temperature
R
Flow-pipe temperature
R
Return-pipe temperature
R
Differential temperature
R
System outlet pressure
R
Actual level in the feed tank
R
Fault code, subpump 1
R
Total operating time, subpump 1
R
Actual speed, subpump 1
R
Fault code, subpump 2
R
Total operating time, subpump 2
R
Actual speed, subpump 2
R
Fault code, subpump 3
R
Total operating time, subpump 3
R
Actual speed, subpump 3
R
Fault code, subpump 4
R
Total operating time, subpump 4
R
Actual speed, subpump 4
R
Fault code, subpump 5
R
Total operating time, subpump 5
R
Actual speed, subpump 5
R
Fault code, subpump 6
R
Total operating time, subpump 6
R
Actual speed, subpump 6
R
Temperature at external temperature sensor 2
R
User-defined setpoint
R
Analog setpoint influence
Unit
-
-
%
bar
-
3
-
m
/h
%
%
M
W
bar
H
S
bar
-
°C
H
-
°C
-
%
H
S
3
H
-
kWh/m
h
kWh
°C
-
-
°C
-
-
°C
-
-
°C
-
-
bar
-
S
m
H
-
-
h
%
-
h
%
-
-
h
-
%
-
-
-
h
-
%
-
-
-
-
h
-
-
%
-
-
-
-
-
h
-
-
%
-
-
°C
-
%
%
H
S
S
S
S
S
H
S
H
S
S
-
H
-
S
S
H
S
H
S
H
S
-
S
-
S
H
S
H
H
H
H
H
H
H
-
H
-
H
25