4.7

Setting device control parameters (SEt)

Open menu "SEt" to configure the device control.
Display
Activation
FAC
off
dc
CHd
CHA
nEt
S.Ct
FAC
SYS
FAC Factory settings
Cs
Customer settings
4.8

Reset to factory settings

All settings with the exception of the interface parameters are reset to the factory settings.
1.
Press MENU button (> 1.5 s).
2.
Go to "SEt" and confirm with Enter.
3.
Go to "FAC" and confirm with Enter.
4.9

Showing and deleting the history memory

ADVICE
The history memory saves the measured values for the first fault only. To this end, the history
memory must be empty.
Setting value
Cs
Range
FAC
0. . .999
dc
CHd
CHA
off
on U
on
on U
off
on
Cs
0
Password for parameter setting
Insulation monitoring mode
dc
dc: CCS
t
an
CHd: CHAdeMO
Values R
t
an
and U
t
an
CHA: CHAdeMO
Values R
t
an
System connection test
off
Device test at device start
Restore factory settings
For Bender Service only
isoCHA425HV_D00404_04_M_XXEN/10.2023
ISOMETER® isoCHA425HV
Description
≤ 10 s
, R
and C
if U
FU
FS
e
n
≤ 1 s if R
≤ 100 k
FU
> DC 100 V
n
≤ 10 s if R
≤ 160 k
FS
and C
if U
> DC 50 V
FU
e
n
≤ 1 s if R
≤ 100 k and U
FU
on: if U
≤ DC 100 V
n
on U: if U
> DC 100 V
n
> DC 50 V
> DC 100 V
n
29