Function
2.3.15 Measuring and response times
The measuring time is the period essential for the detection of the measured value. The measuring time is
reflected in the operating time t
necessary measuring pulse duration, which depends on the insulation resistance R
capacitance C
of the system to be monitored. The measuring pulse is generated by the measuring pulse
e
generator integrated in the ISOMETER®. The measuring times for C
System disturbances may lead to extended measuring times. In contrast, the time for the system voltage
measurement U
is independent and considerably shorter.
n
Operating time t
ae
The operating time t
ae
resistance measured value depends on the insulation resistance R
Response delay t
on
The response delay t
on
each alarm message specified in the alarm assignment has its own timer for t
interference suppression in the case of short measuring times.
An alarm message will only be signalled when a limit value of the respective measured value is violated for the
duration of t
. Each time the limit value is violated within the time t
on
Total response time t
The total response time t
Delay on release t
off
The delay on release t
alarm message specified in the alarm assignment has its own timer for t
An alarm message will be signalled until the limit value of the respective measured value is no longer violated
(including hysteresis) for the duration of t
during t
, the delay on release "toff" restarts.
off
Start-up delay t
After connecting the supply voltage U
"t" (0...10 s).
2.3.16 Password protection (on, OFF)
If password protection is activated (on), settings can only be made after entering the password (0...999). For its
activation, see chapter 4.7.
2.3.17 External test/reset button (T/R)
Functions
• Reset = press the external button < 1.5 s
• Reset + self test = press the external button > 1.5 s
• Stop measuring function = press and hold the external button
16
isoCHA425HV_D00404_04_M_XXEN/10.2023
. For the insulation resistance measured value, it is mainly determined by the
ae
is the time required by the ISOMETER® to determine the measured value. The insulation
is set uniformly for all alarm messages in the "t" menu using the parameter "ton", while
an
is the sum of the operating time t
an
can be set uniformly for all alarm messages using the parameter "toff", while each
off
off
, the alarm output is suppressed for the time set in parameter
S
and the response delay t
ae
without interruption. Each time a limit value is no longer violated
and the system leakage
F
, U
, U
and R % are synchronous.
e
L1e
L2e
and the system leakage capacitance C
F
. This delay can be used for
on
, the response delay "ton" restarts.
on
.
off
.
e
.
on