Fig. 41
Fig. 42
Checking the direction of rotation
The connection between the setpoint value and the actual direction of rotation of the drive must be checked.
The check should be carried out as follows:
● Specify a setpoint value of approx. 10% and switch on release of the frequency inverter for a short time (con‐
troller release control inputs (S1IND/STO A and S7IND/STO B) and SW-Step 1+ or controller release (S1IND/
STO A and S7IND/STO B) and SW-Step 1-).
● Check whether the motor shaft rotates in the correct direction when the drive accelerates.
● In addition to a check of the drive, the corresponding actual values and operating messages can be read out
with the keypad unit.
● If the direction of rotation is wrong, for example, two motor phases, e.g. U and V, must be swapped on the
terminals of the frequency inverter. The connection of the frequency inverter on the line side has no effect on
the direction of rotation of the drive.
Set-up of the frequency inverter is completed and can be supplemented by further settings in the PARA menu.
The parameters are selected in such a way that they are sufficient to put the unit into service in most applica‐
tions. The other settings relevant for the application must be checked according to the "Dedrive Compact STO
frequency inverter application notes/operating instructions"  Tab. 1, Page 2.
The keypad unit display the End message, which you should confirm
with the
key. Guided set-up of the frequency inverter is completed
ENT
with a reset and initialisation of the frequency inverter. The Dedrive
Compact STO reports a fault during initialisation.
The Actual Frequency 241 parameter that is defined in the default
settings is displayed when the frequency inverter has initialised without
any errors.
63