6.5.8

Mains connection

6.5.8.1

DIC-2-003 to 010 and DIC-4-002 to 009 frequency inverters

Fig. 19
3ph/400 V AC mains connection
1
Keyed plug-in terminal
2a
Rigid cable
2b
Flexible cable
2c
With wire end ferrule without plastic sleeve
2d
With wire end ferrule with plastic sleeve
Tab. 32
6.5.8.2

DIC-2-018 and DIC-4-014 to 040 frequency inverters

Fig. 20
3ph/400 V AC mains connection
1
Connection terminals
2a
Rigid cable
2b
Flexible cable
2c
With wire end ferrule without plastic sleeve
2d
With wire end ferrule with plastic sleeve
Tab. 33
42
DIC-2-003 to 005 and DIC-4-002 to 004
Phoenix ZEC 1,5 / ... ST 7,5 (1a)
0,25 ... 1,5 mm
0,25 ... 1,5 mm
DIC-2-018 and DIC-4-014 to 017
WAGO series 745/6 mm
/RM7,5
2
0,2 ... 6 mm
; AWG 24 ... 10
2
0,2 ... 6 mm
; AWG 24 ... 10
2
0,25 ... 4 mm
; AWG 22 ... 12
2
0,25 ... 4 mm
; AWG 22 ... 16
2
DIC-2-010 and DIC-4-006 to 009
Phoenix ZEC 1,5 / ... ST 7,5 (1b)
0,2 ... 1,5 mm
; AWG 24 ... 16
2
0,2 ... 1,5 mm
; AWG 24 ... 16
2
; AWG 22 ... 16
2
; AWG 22 ... 16
2
DIC-4-025 to 040
WAGO series 745/16 mm
0,2 ... 16 mm
; AWG 24 ... 6
2
0,2 ... 16 mm
; AWG 24 ... 6
2
0,25 ... 10 mm
; AWG 22 ... 8
2
0,25 ... 10 mm
; AWG 22 ... 8
2
/RM10+15
2