Data set
Fig. 39
Motor Data
The motor data that needs to be entered in the following guided set-up sequence must be taken from the rating
plate and the motor data sheet. The other motor data required for the control and regulation processes are calcu‐
lated from the settings made during the setup which are checked for plausibility.
Multi-motor operation is possible with Dedrive Compact STO units. Ensure that identical motors and motor cable
lengths are used. The sum of the motors must be entered for the rated current and rated output details for multi-
motor drives.
The default rated values must be checked and, if necessary, changed by the user. Change the values with the ▲
▼ keys and confirm entry with the
Enter the lower of the two voltages for Demag ZBA motors with a wide voltage range, e.g. 380 - 400 V.
Parameters
No.
Name
369
Motor type
370
Rated voltage
371
Rated current
372
Rated speed
374
Rated Cosinus Phi
375
Rated frequency
376
Rated Mech. Power
812
Cyclic duration factor
1014
Rotor type
1015
Motor ambient temperature
490
Operation Mode Encoder 1
491
Division Marks Encoder 1
493
Operation Mode Encoder 2
494
Division Marks Encoder 2
766
Source Actual Speed
Tab. 54
Plausibility check
A check of the motor data should only be omitted by qualified users. The configurations include complex regula‐
tion processes which largely depend on correctly entered motor data. Therefore the warning and error messages
displayed during the check must be observed. If a critical situation is detected during the guided set-up procedure,
it is displayed on the keypad unit. In Parcom Compact, this is displayed in the
Status of motor parameter identification 797 parameter. Depending on the deviation from the ex‐
pected parameter value, a warning or error message is displayed.
The warning message can be acknowledged with the
values entered can be corrected by subsequently pressing the
Possible warning messages during the plausibility check
The warning message can be acknowledged with the
The parameter values entered can be corrected by subsequently pressing the
In Parcom Compact the parameter Motor parameter identification 796 must be set to "1 – Continue".
Warning messages
Code
Measures/remedy
SA000
No warning message existing. This message can be read out via an optional communication card.
SA001
Rated voltage 370 is outside the frequency inverter nominal voltage range. The maximum rated voltage is indicated on the type plate of the
frequency inverter.
SA002
The Rated current 371, Rated Mech. Power 376 and Rated voltage 370 must be checked. The calculated efficiency is in the limit
range for an asynchronous motor.
SA003
Rated Cosinus Phi 374 is outside the standard range (0,6 to 0,95).
Selection of the data set is displayed following configuration. Select the
required Data set dS with the ▲ ▼ keys and confirm with the
Data sets 1 to 4 are saved with the same parameter values in data set
0 (default).
key.
ENT
Unit
Min.
-
0 - Unknown
2 - Synchronous
[V]
60,0
[A]
Depends on type
Depends on type
[rpm]
96
-
0,01
[Hz]
10,00
1000,00
[kW]
Depends on type
Depends on type
40 - 40% CDF
100 - 100% CDF
-
1 - Cylindrical ro‐
2 - Conical rotor
tor
[°C]
40 – 40 ... 49
70 – 70 ... 79
-
1 - single
4 - quadruple
-
1
-
4 - quadruple
104 - 4 x inverted
-
1
-
1 - Encoder 1
2 - Encoder 2
ENT
ENT
Setting
Explanation
Max.
Default
1 - Asynchronous
800,0
U
FUN
I
FUN
60000
Depends on type
1,00
Depends on type
50,00
P
FUN
60 - 60% CDF
1 - Cylindrical ro‐
tor
60 – 60 ... 69
0 - off
Only for Configuration 2xx
8192
1024
Only for Configuration 2xx
0 - off
Only for Configuration 2xx and with
extension module
8192
1024
2 - Encoder 2
Only for Configuration 2xx
key and guided set-up is continued. The parameter
key.
ESC
key and plausibility check is continued.
key.
ESC
key.
ENT
59