6.5.5

Block diagram

Fig. 18
CAUTION
An incorrect DC load may damage the component.
For DC, the relay contact must not be subjected to inductive load. Operation of a 24 V DC coupling relay is not
permitted.
The coil of the attached AC contactor must be provided with an RC filter.
Relay connection
A
S3OUT
Digital Input
B
S1IND/STO A and S7IND/STO B
Digital Input
C
S2IND ... S6IND
D
Digital output S1OUT
E
Multi-function Output MFO1
F
Multi-function Input MFI1
G
24 V power supply
Tab. 30
40
Changeover contact:
Response time approx. 40 ms
Normally open:
240 V AC/5 A (ohmic and inductive); 24 V DC/5 A (ohmic load)
Normally closed:
240 V AC/3 A (ohmic and inductive); 24 V DC/1 A (ohmic load)
The coil of the attached AC contactor must be provided with an RC filter.
Controller release, response time approx. 150 ms (On), 10 ms (Off)
Digital signal:
U
= 30 V, 10 mA at 24 V, PLC-compatible
max
Response time approx. 2 ms, U
Digital signal:
Frequency signal:
0 ... 30 V, 10 mA at 24 V, f
24 V, I
Digital signal:
max
24 V, I
Digital signal:
max
24 V, I
Analogue signal:
max
Frequency signal:
0 ... 24 V, I
Digital signal:
Response time approx. 4 ms, U
Analogue signal:
Resolution 12 Bit, 0 ... 10 V (Ri = 70 kΩ), 0 ... 20 mA (Ri = 500 Ω)
Bi-directional control ter‐
see  "External 24 V power supply", Page 41 and "Dedrive Compact STO frequen‐
minals
cy inverter application notes/operating instructions"
= 30 V, 10 mA at 24 V, PLC-compatible
max
= 150 kHz
max
=40 mA, PLC-compatible, overload proof and short-circuit proof
=40 mA, PLC-compatible, overload proof and short-circuit proof
= 40 mA, pulse width modulated, f
PWM
= 40 mA, f
= 150 kHz
max
max
= 30 V, 0,4 mA at 24 V, PLC-compatible
max
= 116 Hz