DEMAG DIC 002 Series Operating Instructions Manual page 60

Table of Contents

Advertisement

Warning messages
Code
Measures/remedy
SA004
The Rated speed 372 and the Rated frequency 375 must be checked. The slip for an asynchronous motor is in the limit range.
SA054
Resolver offset not set
Tab. 55
Possible error messages during the plausibility check
If an error message appears, check and enter the programmed rated data again. Parameter identification must be
restarted. Only experienced users should prematurely terminate parameter identification by pressing the
key, since some of the rated data is not correct.
Error messages
Code
Measures/remedy
SF000
No error message existing.
SF001
The rated current 371 that was entered is too low.
SF002
The Rated current 371 is too high with reference to Rated Mech. Power 376 and Rated voltage 370.
SF003
Rated Cosinus Phi 374 is incorrect (more than 1 or less than 0,3).
SF004
Slip Frequency calculated from the rated data is negative. The Rated speed 372 and the Rated frequency 375 must be checked.
SF005
The Rated speed 372 and the Rated frequency 375 that were entered must be checked, since the calculated Slip Frequency is too large.
SF006
The total power of the drive calculated from the rated data is smaller than the entered rated power.
SF007
The set configuration is not supported by guided set-up.
Tab. 56
Please correct the values and repeat the parameter identification run following an SFxyz error message.
Parameter identification
The selected configuration requires further motor data that are not specified on the motor rating plate. Parameter
identification measures the necessary motor data. The values measured when the drive is at standstill are en‐
tered direct or after calculation of the parameter. The parameter identification sequence and duration varies ac‐
cording to the motor connected and the unit rating and can take up to several minutes. The connected motor is
evaluated in the course of parameter identification with the displayed signals. During this procedure the drive can
be braked firmly.
Guided set-up switches over to the parameter identification functions after the entered motor data have been
checked.
Press the
ENT
In Parcom Compact the function is started by setting the parameter status of
Motor parameter identification 796 to the value "10 - Complete Setup, DS0".
The "Safe Torque Off" STO safety function of the frequency inverter prevents release of the power section if the
S1IND / STO A and S7IND / STO B digital input (controller release) is not activated.
If the control release signal is not applied to S1IND STO A and S7IND / STO B, the inverter displays "StO" on the
keypad unit. When the release signal is applied, the "StO" message is deleted and the unit starts identifying the
parameters.
DANGER
Inappropriate commissioning
Danger to life and limb.
Inappropriate commissioning may result in personal injury or material damage.
This work may only be carried out in compliance with the safety regulations by authorised and trained per‐
sonnel who are familiar with the frequency inverter operating functions.
The frequency inverter may only be put into service by personnel who are fully familiar with the operating
instructions. In particular, they contain the "Safety" section and the relevant safety instructions in the work‐
ing sections of these operating instructions.
Parameter identification of the frequency inverter requires release of the power module.
The final "rEAdY" message must be confirmed by pressing the
Any installed du/dt filter must be disconnected for parameter identification.
60
key to confirm the "PAidE" message.
key.
ENT
ESC