Electrical Specifications; Grounding; Circuit Breaker; System Ac Power Specifications - HP Integrity rx8620 User's & Service Manual

Hide thumbs Also See for Integrity rx8620:
Table of Contents

Advertisement

Electrical Specifications

This section provides electrical specifications for the HP Integrity rx8620 Server.

Grounding

The site building shall provide a safety ground and protective earth for each AC service entrance to all
cabinets.
Install a protective earthing (PE) conductor that is identical in size, insulation material, and thickness to the
branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing
conductor described is to be connected from the unit to the building installation earth or if supplied by a
separately derived system, at the supply transformer or motor-generator set grounding point.

Circuit Breaker

The Marked Electrical for the HP Integrity rx8620 Server is 15 amps per line cord. The recommended circuit
breaker size is 20 amps for North America. For countries outside North America, consult your local electrical
authority having jurisdiction for the recommended circuit breaker size.
The HP Integrity rx8620 Server contains four C20 power receptacles located at the bottom rear bulkhead. A
minimum of two power cords must be used to maintain normal operation of the HP Integrity rx8620 Server. A
second set of two cords can be added to improve system availability by protecting, for example, against power
source failures or accidentally tripped circuit breakers. The HP Integrity rx8620 Server can receive AC input
from two different AC power sources.

System AC Power Specifications

Power Cords
Table B-3 lists the various power cables available for use with a HP Integrity rx8620 Server system. Each
power cord is 15 feet (4.5-m) in length with a IEC 60320-1 C19 female connector attached to one end.
Table B-3
Power Cords
Part Number
8120-6895
Stripped end, 240 volt
8120-6897
Male IEC309, 240 volt
8121-0070
Male GB-1002, 240 volt
8120-6903
Male NEMA L6-20, 240 volt
Appendix B
Description
Where Used
International - Other
International
China
North America/Japan
System Specifications
Electrical Specifications
177