Electrical Specifications - HP Integrity Superdome 2 16-socket Service Manual

Hp integrity superdome 2 user service guide
Hide thumbs Also See for Integrity Superdome 2 16-socket:
Table of Contents

Advertisement

Electrical specifications

Table 5 Compute enclosure power options
Source type
3–phase
3–phase
Single-phase
NOTE:
When wiring a 3-phase enclosure, phase rotation is unimportant.
Table 6 Single-phase power cords
Part number
8120-6895
8120-6897
8121-0070
8120-6903
Table 7 Compute enclosure single-phase HP 2400 W power supply specifications
Specification
Power cord
Output
Input requirements
Rated input voltage
Rated input frequency
Rated input current per power supply (maximum)
Maximum inrush current
Ground leakage current
Power factor correction
Table 8 Compute enclosure 3-phase HP 2400 W power supply specifications (North America/Japan)
Specification
Power cords (4)
Source voltage
Plug or connector
(nominal)
type
200–220 VAC
NEMA L15-30p,
line-to-line
3-Pole, 4-wire, 3m
(phase-to-phase),
(10ft) power cord
3–phase
50Hz/60Hz
220 VAC to 240
IEC 309, 4–pole,
VAC line-to-neutral
5–wire, Red, 3m
3–phase
(10ft) power cord
50Hz/60Hz
200V to 240V ac
IEC 320
50Hz/60Hz
C19-C20
Description
Stripped end, 240 V
Male IEC309, 240 V
Male GB- 1 002, 240 V
Male NEMA L6-20, 240 V
Power receptacle
Circuit type
required
30A 3-phase
L15-30R. 3-pole,
4-wire
16A
IEC 309, 4–pole,
5–wire, red
16A/20A
IEC 320
Single-phase
C19
Where used
International - other
International
China
North America/Japan
Value
IEC-320 C19-C20
2400 W per power supply
200 VAC to 240 VAC
50-60 Hz
13.8 A at 200 VAC
13.3 A at 208 VAC
12.6 A at 220 VAC
100 A for 10 ms
1.16 mA
0.98
Value
NEMA L15-30p
Number of power
cords required (per
enclosure)
4
4
12
Electrical specifications
23

Advertisement

Table of Contents
loading

Table of Contents